6–16
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 6: ACTUAL VALUES
The values for analog inputs are shown here. The name of the input and the units will
reflect those programmed for each input. If no analog inputs are programmed in
S12
ANALOG I/O
ANALOG INPUT 1(4)
, the
THIS FEATURE NOT PROGRAMMED
flash
message will appear when an attempt is made to enter this group of messages.
6.3.8
Phasors
PATH: ACTUAL VALUES
A2 METERING DATA
PHASORS
The 469 Motor Management Relay was designed to display lagging angles. Therefore, if a
system condition would cause the current to lead the voltage by 45°, the 469 relay will
display such angle as 315° Lag instead of 45° Lead.
NOTE
Note
When the currents and voltages measured by the relay are zero, the angles displayed
by the relay and those shown by the EnerVista 469 Setup software are not fixed values.
The EnerVista 469 Setup software is a useful tool to view the vectors seen by the relay in
graphical format. The same information described above is displayed by the EnerVista 469
Setup software as follows:
PHASORS
[
]
Va PHASOR
0.0% AT 0°Lag
MESSAGE
Vb PHASOR
0.0% AT 0°Lag
MESSAGE
Vc PHASOR
0.0% AT 0°Lag
MESSAGE
Ia PHASOR
0.0% AT 0°Lag
MESSAGE
Ib PHASOR
0.0% AT 0°Lag
MESSAGE
Ic PHASOR
0.0% AT 0°Lag
Summary of Contents for Masoneilan 469 Series
Page 4: ......
Page 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Page 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Page 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...