CHAPTER 6: ACTUAL VALUES
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
6–5
Immediately prior to issuing a trip, the 469 takes a snapshot of motor parameters and
stores them as pre-trip values that allow for troubleshooting after the trip occurs. The
CAUSE OF LAST TRIP
message is updated with the current trip and the screen defaults to
that message. All trip features are automatically logged as date and time stamped events
as they occur. This information may include motor speed (2-Speed feature or Assignable
Digital Input), phase and ground currents, RTD temperatures, voltages, frequency, power
quantities, and analog inputs. This information can be cleared using the
S1 469 SETUP
CLEAR DATA
CLEAR LAST TRIP DATA
settings.
The
CAUSE OF LAST TRIP
actual value has the following range: No Trip to Date, Incomplete
Sequence, Remote Trip, Speed Switch, Load Shed, Pressure Switch, Vibration Switch,
General Sw, Overload, Short Circuit, Mechanical Jam, Undercurrent, Current Unbalance,
Ground Fault, Phase Differential, Acceleration, Tachometer, RTDs #1 to #12, Undervoltage,
Overvoltage, Phase Reversal, Frequency, Reactive Power, Power Factor, Underpower,
Analog Inputs 1 to 4, Single Phasing, Reverse Power, Analog Diff 1-2, Analog Diff 3-4, and
Loss of Comms Trip.
MESSAGE
HOTTEST STATOR RTD
RTD #1: 0°C PreTrip
Range: –50 to 250°C or –58 to 482°F.
Seen only if at least 1 RTD is set
as Stator
MESSAGE
HOTTEST BEARING RTD
RTD #7: 0°C PreTrip
Range: –50 to 250°C or –58 to 482°F.
Seen only if at least 1 RTD is set
as Bearing
MESSAGE
HOTTEST OTHER RTD
RTD #11: 0°C PreTrip
Range: –50 to 250°C or –58 to 482°F.
Seen only if at least 1 RTD is set
as Other
MESSAGE
AMBIENT RTD
RTD#12: 0°C PreTrip
Range: –50 to 250°C or –58 to 482°F.
Seen only if at least 1 RTD is set
as Ambient
MESSAGE
Vab:
0
Vbc:
0
Vca:
0
V PreTrip
Range: 0 to 20000 V. Not seen if VT
Connection is set as None
MESSAGE
Van:
0
Vbn:
0
Vcn:
0
V PreTrip
Range: 0 to 20000 V. Seen only if VT
Connection is set as Wye
MESSAGE
PRETRIP SYSTEM
FREQUENCY: 0.00 Hz
Range: Not seen if VT Connect. set as
None
MESSAGE
0 kW
0 kVA
0 kvar
PreTrip
Range: –50000 to 50000 kVA. Not seen
if VT Connection set as None
MESSAGE
POWER FACTOR
PreTrip: 0.00
Range: 0.01 to 0.99 Lead or Lag, 0.00,
1.00. Not seen if VT Connection
is set as “None”
MESSAGE
Analog I/P 1
PreTrip: 0 Units
Range: –50000 to 50000. Not seen if
Analog Input 1 is “Disabled”.
MESSAGE
Analog I/P 2
PreTrip: 0 Units
Range: –50000 to 50000. Not seen if
Analog Input 2 is “Disabled”.
MESSAGE
Analog I/P 3
PreTrip: 0 Units
Range: –50000 to 50000. Not seen if
Analog Input 3 is “Disabled”.
MESSAGE
Analog I/P 4
PreTrip: 0 Units
Range: –50000 to 50000. Not seen if
Analog Input 4 is “Disabled”.
Summary of Contents for Masoneilan 469 Series
Page 4: ......
Page 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Page 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Page 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...