5–106
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
5.15 S14 Two-Speed Motor
5.15.1 Description
The two-speed motor feature provides proper protection for a two-speed motor where
there will be two different full load values. The algorithm integrates the heating at each
speed into one thermal model using a common thermal capacity used register value for
both speeds.
If the two-speed motor feature is used, Assignable Input 4 is dedicated as the two-speed
motor monitor and terminals D22 and D23 are monitored for a contact closure. Contact
closure signifies that the motor is in Speed 2; if the input is open, it signifies that the motor
is in Speed 1. This allows the 469 to determine which settings should be active at any given
point in time. Two-speed motor protection is enabled with the
S2 SYSTEM SETUP
CURRENT
SENSING
ENABLE 2-SPEED MOTOR PROTECTION
settings.
Speed2 Overload Setup
•
Overview
The settings corresponding to the Speed2 Overload Curve are closely related to the
Thermal Model curve style and overload curve settings. Refer to 5.6.2
on page 5–41 for details. When setting the
Speed2 Overload Curve characteristics, only the relevant settings corresponding to the
overload curve style will be shown, as described below.
•
Standard Overload Curves
If the
SELECT CURVE STYLE
is set to “Standard” in the Thermal Model, the following settings
will appear:
PATH: SETTINGS
S14 2-SPEED MOTOR
SPEED2 OVERLOAD SETUP
on page 5–41 for additional details on the standard
overload curves available for Speed2.
•
Custom Overload Curves
If the
SELECT CURVE STYLE
is set to “Custom” in the Thermal Model, the following settings
will appear:
PATH: SETTINGS
S14 2-SPEED MOTOR
SPEED2 OVERLOAD SETUP
SPEED2
[
]
OVERLOAD SETUP
SPEED2 STANDARD
CURVE NUMBER: 4
Range: 1 to 15 in steps of 1
SPEED2
[
]
OVERLOAD SETUP
SPEED2 TRIP AT
1.01 x FLA: 17414.5 s
Range: 0.5 to 99999.9 in steps of 0.1
MESSAGE
SPEED2 TRIP AT
1.05 x FLA: 3414.9 s
Range: 0.5 to 99999.9 in steps of 0.1
MESSAGE
SPEED2 TRIP AT
1.10 x FLA: 1666.7 s
Range: 0.5 to 99999.9 in steps of 0.1
MESSAGE
SPEED2 TRIP AT
1.20 x FLA: 795.4 s
Range: 0.5 to 99999.9 in steps of 0.1
Summary of Contents for Masoneilan 469 Series
Page 4: ......
Page 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Page 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Page 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...