8.3.4.7
Vib 1-8
[ ] = defaults
Name
Direction
Data
Type
Description
VIB_CalcSel
TMR_DiffLimt
Filter
Type
Filtrhpcutoff
VIB1
AnalogInput
REAL
Vibration displacement (pk-pk)
or velocity (pk), AC component
of input#1
[ VIB_Pk-Pk ]
Vib_RMS
‡
Difference Limit
for Voted TMR
Inputs in Volts or
Mils
[2]
-100 to 100
Filter
used for
Velomitor
and
Seismic
only
[None],
Low
Pass,
High
Pass,
Band
Pass
High Pass 3db
point (cutoff in Hz)
[6]
4 to 300
↓
↓
↓
↓
VIB8
AnalogInput
REAL
Vibration displacement (pk-pk)
or velocity (pk), AC component
of input#8
‡
Vib_RMS is only valid when OperatingMode is Enhanced and when using YVIBS1B.
fltrlpattn
Filtrlpcutoff
fltrlppattn
SysLim1Enabl
SysLim1Latch
SysLim1Type
SysLimit1
Slope or
attenuation of
high pass filter
after cutoff
[2-pole],
4-pole,
6-pole,
8-pole,
10-pole
Low Pass 3db
point (cutoff in
Hz)
[500]
15 to 4300
Slope or
attenuation of
low pass filter
after cutoff
[2-pole]
4-pole,
6-pole,
8-pole,
10-pole
Enable System
Limit 1
[Disable], Enable
Latch the alarm
[Latch], NotLatch
System Limit 1
Check Type
[ >= ], <=
System Limit 1 –
GAP in negative
volts (Velomitor)
or positive mils
(Prox)
[50]
-100 to 100
SysLim2Enabl
SysLim2Latch
SysLim2Type
SysLimit2
Enable System Limit 2
[Disable], Enable
Latch the alarm
[Latch], NotLatch
System Limit 2 Check
Type
[ >= ], <=
System Limit 2 – GAP in negative volts (Velomitor)
or positive mils (Prox)
[0]
-100 to 100
YVIB Vibration Monitor Modules
GEH-6855_Vol_II System Guide 265
Public Information