3.2.2
IONet Switches
IONet switches are unmanaged, fully switched, and full-duplex to prevent collisions. They provide data buffering and flow
control during the critical input scan. Only industrial grade switches that meet the codes, standards, performance, and
environmental criteria for industrial applications are used for the IONet. GE industrial Ethernet 10/100 IONet switches
(ESWA and ESWB) have an operating temperature of -40 to 70 °C (-40 to 158 °F), have provisions for redundant 18 to 36 V
dc power sources (200/400 mA), and can be DIN-rail mounted. The switches also provide LEDs to indicate the status of the
IONet link, speed, activity, and duplex.
16-port ESWB IONet Switch
Caution
Use only GE-approved Ethernet switches in all control system I/O networks.
Unsupported switches can prevent I/O modules from receiving controller outputs.
Approved IONet Switches
Part #
Description
IS420ESWAH1A
8 ports 10/100BASE-TX + 1 port 100BASE-FX LC-type connection
IS420ESWAH2A
8 ports 10/100BASE-TX + 2 ports 100BASE-FX LC-type connection
IS420ESWAH3A
8 ports 10/100BASE-TX
IS420ESWAH4A
8 ports 10/100BASE-TX + 1 port 100BASE-LX10 LC-type connection
IS420ESWAH5A
8 ports 10/100BASE-TX + 2 ports 100BASE-LX10 LC-type connection
IS420ESWBH1A
16 ports 10/100BASE-TX + 1 port 100BASE-FX LC-type connection
IS420ESWBH2A
16 ports 10/100BASE-TX + 2 ports 100BASE-FX LC-type connection
IS420ESWBH3A
16 ports 10/100BASE-TX
IS420ESWBH4A
16 ports 10/100BASE-TX + 1 port 100BASE-LX10 LC-type connection
IS420ESWBH5A
16 ports 10/100BASE-TX + 2 ports 100BASE-LX10 LC-type connection
Part #
Description
336A4940DNP508TX
8 copper ports
336A4940DNP516TX
16 copper ports
336A4940DNP509FX
8 copper ports and 1 fiber port
336A4940DNP517FX
16 copper ports and 1 fiber port
336A4940DNP508FXE2
6 copper ports and 2 fiber ports (single mode)
336A4940JEP001
Installed within the 1.x ESS wind turbine hub
336A4940JEP002
Installed within the 1.x wind turbine top box
336A4940JEP003
Installed within the 1.x wind turbine Down Tower Assembly (DTA)
336A4940JEP004
Installed within the 2.x and 1.x non-ESS wind turbine hub
82
GEH-6721_Vol_I_BP
GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I
Public Information