![GE M60 UR Series Instruction Manual Download Page 207](http://html.mh-extra.com/html/ge/m60-ur-series/m60-ur-series_instruction-manual_130365207.webp)
GE Multilin
M60 Motor Protection System
5-79
5 SETTINGS
5.2 PRODUCT SETUP
5
5.2.13 USER-PROGRAMMABLE PUSHBUTTONS
PATH: SETTINGS
PRODUCT SETUP
USER-PROGRAMMABLE PUSHBUTTONS
USER PUSHBUTTON 1(16)
The optional user-programmable pushbuttons (specified in the order code) provide an easy and error-free method of enter-
ing digital state (on, off) information. The number of available pushbuttons is dependent on the faceplate module ordered
with the relay.
•
Type P faceplate: standard horizontal faceplate with 12 user-programmable pushbuttons.
•
Type Q faceplate: enhanced horizontal faceplate with 16 user-programmable pushbuttons.
The digital state can be entered locally (by directly pressing the front panel pushbutton) or remotely (via FlexLogic oper-
ands) into FlexLogic equations, protection elements, and control elements. Typical applications include breaker control,
autorecloser blocking, and setting groups changes. The user-programmable pushbuttons are under the control level of
password protection.
The user-configurable pushbuttons for the enhanced faceplate are shown below.
USER PUSHBUTTON 1
PUSHBUTTON 1
FUNCTION: Disabled
Range: Self-Reset, Latched, Disabled
MESSAGE
PUSHBTN 1 ID TEXT:
Range: Up to 20 alphanumeric characters
MESSAGE
PUSHBTN 1 ON TEXT:
Range: Up to 20 alphanumeric characters
MESSAGE
PUSHBTN 1 OFF TEXT:
Range: Up to 20 alphanumeric characters
MESSAGE
PUSHBTN 1 HOLD:
0.0 s
Range: 0.0 to 10.0 s in steps of 0.1
MESSAGE
PUSHBTN 1 SET:
Off
Range: FlexLogic operand
MESSAGE
PUSHBTN 1 RESET:
Off
Range: FlexLogic operand
MESSAGE
PUSHBTN 1 AUTORST:
Disabled
Range: Disabled, Enabled
MESSAGE
PUSHBTN 1 AUTORST
DELAY: 1.0 s
Range: 0.2 to 600.0 s in steps of 0.1
MESSAGE
PUSHBTN 1 REMOTE:
Off
Range: FlexLogic operand
MESSAGE
PUSHBTN 1 LOCAL:
Off
Range: FlexLogic operand
MESSAGE
PUSHBTN 1 DROP-OUT
TIME: 0.00 s
Range: 0 to 60.00 s in steps of 0.05
MESSAGE
PUSHBTN 1 LED CTL:
Off
Range: FlexLogic operand
MESSAGE
PUSHBTN 1 MESSAGE:
Disabled
Range: Disabled, Normal, High Priority
MESSAGE
PUSHBUTTON 1
EVENTS: Disabled
Range: Disabled, Enabled
Summary of Contents for M60 UR Series
Page 10: ...x M60 Motor Protection System GE Multilin TABLE OF CONTENTS ...
Page 128: ...4 30 M60 Motor Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 410: ...5 282 M60 Motor Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 440: ...6 30 M60 Motor Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 452: ...7 12 M60 Motor Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 462: ...9 8 M60 Motor Protection System GE Multilin 9 2 BATTERIES 9 MAINTENANCE 9 ...
Page 474: ...A 12 M60 Motor Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 584: ...B 110 M60 Motor Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 614: ...C 30 M60 Motor Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 630: ...E 10 M60 Motor Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 642: ...F 12 M60 Motor Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 644: ...G 2 M60 Motor Protection System GE Multilin G 1 RADIUS SERVER CONFIGURATION APPENDIX G G ...
Page 652: ...H 8 M60 Motor Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 662: ...x M60 Motor Protection System GE Multilin INDEX ...