GE Multilin
M60 Motor Protection System
5-23
5 SETTINGS
5.2 PRODUCT SETUP
5
Users logged in through the front panel are not timed out and cannot be forcefully logged out by a
supervisor. Roles logged in through the front panel that do no allow multiple instances (Administrator,
Supervisor, Engineer, Operator) must switch to None (equivalent to a logout) when they are done in
order to log out.
For all user roles except Observer, only one instance can be logged in at one time, for both login by
front panel and software.
To configure server authentication:
1.
In the EnerVista software, choose device authentication and log in as Administrator.
2.
Configure the following RADIUS server parameters: IP address, authentication port, shared secret, and vendor ID.
3.
On the RADIUS server, configure the user accounts. Do not use the five pre-defined roles as user names (Administra-
tor, Supervisor, Engineer, Operator, Observer) in the RADIUS server. If you do, the UR relay automatically provides the
authentication from the device.
4.
In the EnerVista software, choose server authentication and log in using the user name and password configured on
the RADIUS server for server authentication login.
5.
After making any required changes, log out.
When changing settings offline, ensure that only settings permitted by the role that performs the set-
tings download are changed because only those changes are applied.
Pushbuttons (both user-control buttons and user-programmable buttons) located on the front panel can be pressed by an
Administrator or Engineer role. This also applies to the reset button, which resets targets, where targets are errors dis-
played on the front panel or the Targets panel of the EnerVista software. The reset button has special behavior in that it
allows these two roles to press it even when they are logged in through the RS232 port and not through the front panel.
To reset the security event log and self-test operands:
1.
Log in as Supervisor (if the role is enabled) or Administrator (if the Supervisor role is disabled) and execute a clear
security command under
Commands > Security > Clear Security
.
5.2.2 DISPLAY PROPERTIES
PATH: SETTINGS
PRODUCT SETUP
DISPLAY PROPERTIES
Some relay messaging characteristics can be modified to suit different situations using the display properties settings.
DISPLAY
PROPERTIES
LANGUAGE:
English
Range: English; English, French; English, Russian;
English, Chinese; English, German
(range dependent on order code)
MESSAGE
FLASH MESSAGE
TIME: 1.0
s
Range: 0.5 to 10.0 s in steps of 0.1
MESSAGE
DEFAULT MESSAGE
TIMEOUT: 300 s
Range: 10 to 900 s in steps of 1
MESSAGE
DEFAULT MESSAGE
INTENSITY: 25 %
Range: 25%, 50%, 75%, 100%
Visible only if a VFD is installed
MESSAGE
SCREEN SAVER
FEATURE: Disabled
Range: Disabled, Enabled
Visible only if an LCD is installed
MESSAGE
SCREEN SAVER WAIT
TIME: 30 min
Range: 1 to 65535 min. in steps of 1
Visible only if an LCD is installed
MESSAGE
CURRENT CUT-OFF
LEVEL: 0.020 pu
Range: 0.002 to 0.020 pu in steps of 0.001
MESSAGE
VOLTAGE CUT-OFF
LEVEL: 1.0 V
Range: 0.1 to 1.0 V secondary in steps of 0.1
Summary of Contents for M60 UR Series
Page 10: ...x M60 Motor Protection System GE Multilin TABLE OF CONTENTS ...
Page 128: ...4 30 M60 Motor Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 410: ...5 282 M60 Motor Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 440: ...6 30 M60 Motor Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 452: ...7 12 M60 Motor Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 462: ...9 8 M60 Motor Protection System GE Multilin 9 2 BATTERIES 9 MAINTENANCE 9 ...
Page 474: ...A 12 M60 Motor Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 584: ...B 110 M60 Motor Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 614: ...C 30 M60 Motor Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 630: ...E 10 M60 Motor Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 642: ...F 12 M60 Motor Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 644: ...G 2 M60 Motor Protection System GE Multilin G 1 RADIUS SERVER CONFIGURATION APPENDIX G G ...
Page 652: ...H 8 M60 Motor Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 662: ...x M60 Motor Protection System GE Multilin INDEX ...