CHAPTER 6: ACTUAL VALUES
STATUS
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
6-5
6
6.3.3 RxGOOSE boolean inputs
ACTUAL VALUES
STATUS
RxGOOSE BOOLEANS
6.3.4 RxGOOSE DPS inputs
ACTUAL VALUES
STATUS
RxGOOSE DPS
6.3.5 Direct inputs
ACTUAL VALUES
STATUS
DIRECT INPUTS
The present state of the direct inputs from communications channels 1 and 2 display here. The state displayed is that of
the remote point unless channel 1 or 2 has been declared to have “failed”, in which case the value shown is the
programmed default state defined in the
SETTINGS
INPUTS/OUTPUTS
DIRECT
DIRECT INPUTS
menu.
6.3.6 Contact outputs
ACTUAL VALUES
STATUS
CONTACT OUTPUTS
RxGOOSE BOOLEANS
RxGOOSE BOOLEAN 1
STATUS: Off
Range: On, Off
RxGOOSE BOOLEAN 256
STATUS: Off
Range: On, Off
The L90 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time
of ordering. See the Order Codes section of chapter 2 for details.
RxGOOSE DPS
RxGOOSE DPS 1
Status: Intermediate
Range: On, Off, Intermediate, Bad
RxGOOSE DPS 16
Status: Intermediate
Range: On, Off, Intermediate, Bad
The L90 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time
of ordering. See the Order Codes section of chapter 2 for details.
DIRECT INPUTS
DIRECT INPUT 1-1:
Off
Range: On, Off
DIRECT INPUT 1-8:
Off
Range: On, Off
DIRECT INPUT 2-1:
Off
Range: On, Off
DIRECT INPUT 2-8:
Off
Range: On, Off
CONTACT OUTPUTS
Cont Op 1
Off
Range: On, Off, VOff, VOn, IOn, IOff