CHAPTER 7: COMMANDS AND TARGETS
TARGETS MENU
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
7-7
7
•
Description of problem
: The
PRODUCT SETUP
INSTALLATION
RELAY SETTINGS
setting indicates the L60 is not
programmed.
•
How often the test is performed
: On power up and whenever the
PRODUCT SETUP
INSTALLATION
RELAY SETTINGS
setting is altered
.
•
What to do
: Program all settings and then set
PRODUCT SETUP
INSTALLATION
RELAY SETTINGS
to “Programmed.”
•
Latched target message
: No.
•
Description of problem
: Internal recovery failure detected.
•
How often the test is performed
: Upon recovery.
•
What to do
: Extract a Service Report through UR Setup software. Contact technical support and supply details of the
failure code on the display.
•
Latched target message
: Yes.
•
Description of problem
: Relay system failure detected.
•
How often the test is performed
: Continuous.
•
What to do
: Extract a Service Report through UR Setup software. Contact technical support and supply details of the
failure code on the display.
7.2.2.3 Minor self-test error messages
Most of the minor self-test errors can be disabled. See the settings in the User-programmable Self-tests section in chapter
5.
•
Latched target message
: Yes.
•
Description of problem
: Transient communication failure detected.
•
How often the test is performed
: Module dependent.
•
What to do
: Extract a Service Report through UR Setup software. Contact technical support and supply details of the
failure code on the display.
•
Latched target message
: Yes.
•
Description of problem
: The battery is weak or not functioning. It powers the real time clock. This message displays as
Battery Fail in the event records. When the battery weakness reaches a critical level, the message displays persistently
on the front panel and no front panel key navigation is possible.
•
How often the test is performed
: The battery is monitored every five seconds. The error message displays after 60
seconds if the problem persists
.
•
What to do
: Replace the battery as outlined in the Maintenance chapter.
•
Latched target message
: No.
•
Description of problem
: Direct input and output settings are configured for a ring, but the connection is not in a ring.
DIAGNOSTIC FAILURE___:
Self Test Error
SYSTEM FAILURE___:
with 2nd line detail
DIAGNOSTIC ALARM:
with 2nd line detail
MAINTENANCE ALERT:
Replace Battery
MAINTENANCE ALERT:
Direct I/O Ring Break