Figure 5-198: POTT scheme logic
5.7.11 Autoreclose (ANSI 79)
SETTINGS
CONTROL ELEMENTS
AUTORECLOSE
AUTORECLOSE
AUTORECLOSE
AR FUNCTION:
Disabled
Range: Disabled, Enabled
AR MODE:
Mode 1 (1 & 3 Pole)
Range: Mode 1(1 & 3 Pole), Mode 2 (1 Pole), Mode 3 (3
Pole-A), Mode 4 (3 Pole-B)
Mode 1 Activation:
Off
Range: FlexLogic operand
Mode 2 Activation:
Off
Range: FlexLogic operand
Mode 3 Activation:
Off
Range: FlexLogic operand
Mode 4 Activation:
Off
Range: FlexLogic operand
AR MAX NUMBER OF
SHOTS: 2
Range: 1, 2, 3, 4
AR INITIATE MODE:
Protection AND CB
Range: Protection AND CB, Protection Only