5-252
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
GROUPED ELEMENTS
CHAPTER 5: SETTINGS
5
The phase instantaneous overcurrent element can be used as an instantaneous element with no intentional delay or as a
definite time element. The input current is the fundamental phasor magnitude. For timing curves, see the publication
Instantaneous Overcurrent (IOC) Element Response to Saturated Waveforms in UR Series Relays (
).
FUNCTION
— This setting enables and disables the phase instantaneous overcurrent protection element.
SOURCE
— Selects the signal source for the phase instantaneous overcurrent protection element.
PICKUP
— Specifies the phase instantaneous overcurrent pickup level in per-unit values.
DELAY
—Delays the assertion of the
PHASE IOC OP
operands. It is used to achieve timing coordination with other elements
and relays.
RESET DELAY
— Specifies a delay for the reset of the phase instantaneous overcurrent element between the operate output
state and the return to logic 0 after the input passes outside the defined pickup range. This setting is used to ensure that
the relay output contacts are closed long enough to ensure reception by downstream equipment.
BLOCK A
— Assertion of the operand assigned to this setting block’s phase A of the phase instantaneous overcurrent
element.
EVENTS
— Enables and disables the logging of phase instantaneous overcurrent events in the sequence of events recorder.
Figure 5-139: Phase instantaneous overcurrent 1 logic
5.6.8.5 Phase directional overcurrent (ANSI 67P, IEC PDOC/PTOC)
SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
PHASE CURRENT
PHASE DIRECTIONAL 1(2)
PHASE IOC1 BLOCK A:
Off
Range: FlexLogic operand
PHASE IOC1 BLOCK C:
Off
Range: FlexLogic operand
PHASE IOC1
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
PHASE IOC1
EVENTS: Disabled
Range: Disabled, Enabled
PHASE
DIRECTIONAL 1
PHASE DIR 1
FUNCTION: Disabled
Range: Disabled, Enabled
PHASE DIR 1 SIGNAL
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
PHASE DIR 1 BLOCK:
Off
Range: FlexLogic operand