5-210
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
GROUPED ELEMENTS
CHAPTER 5: SETTINGS
5
Figure 5-106: Open breaker echo logic
5.6.4 Line pickup
SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
LINE PICKUP
LINE PICKUP
LINE PICKUP
FUNCTION: Disabled
Range: Disabled, Enabled
LINE PICKUP SIGNAL
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
PHASE IOC LINE
PICKUP: 1.000 pu
Range: 0.020 to 30.000 pu in steps of 0.001
LINE PICKUP UV PKP:
0.700 pu
Range: 0.004 to 3.000 pu in steps of 0.001
LINE END OPEN PICKUP
DELAY: 0.150 s
Range: 0.000 to 65.535 s in steps of 0.001
LINE END OPEN RESET
DELAY: 0.090 s
Range: 0.000 to 65.535 s in steps of 0.001
LINE PICKUP OV PKP
DELAY: 0.040 s
Range: 0.000 to 65.535 s in steps of 0.001
SETTING
SETTING
SETTING
SETTING
SETTING
SETTING
SETTING
SETTING
FLEXLOGIC OPERAND
OPEN BREAKER KEYING:
BRK 1 CONTACT SUPV:
BRK 2 CONTACT SUPV:
OPEN BRK KEYING PKP
DELAY: 00.000S
WEEK-INFEED
PICKUP DELAY:
OPEN BRK KEYING RST
DELAY: 00.000S
WEEK-INFEED
RESET DELAY:
WEAK-INFEED
KEYING:
WEAK - INFEED
SUPV:
BRK 1
AUX CONTACT :
Off=0
SETTING
Off=0
Enabled=1
Off=0
Off=0
Off=0
Off=0
OR
AND
AND
AND
AND
AND
827075AA.CDR
87PC BKR ECHO PKP
BRK 2
AUX CONTACT:
t
PKP
=35ms
t
RST
t
PKP
t
RST