4-34
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
FRONT PANEL INTERFACE
CHAPTER 4: INTERFACES
4
The
SETTINGS > INPUTS/OUTPUTS > RESETTING > RESET ANNUNCIATOR
setting can be used to select a FlexLogic
operand that when activated acknowledges/resets all annunciator windows.
Annunciator editor
The annunciator editor is used to configure alarms and actual value displays for the graphical front panel.
The path in the EnerVista software is
Settings > Product Setup > Graphical Panel > Annunciator Editor
.
The figure shows the annunciator editor and its preview window. The page name is entered as General at the top right.
Acknowledgeable and self-resetting alarms are set for basic functions, such as online/offline, Ethernet ports, unauthorized
access/failed logins, and battery failure. The text to display in the annunciator window is entered. The IN SERVICE LED is set
to be green because when the device is on, this LED is green. The preview shows what the annunciator looks like with all
alarms triggered. The last window is not configured and displays blank/grey. In order for the Ethernet and battery alarms
to work, the corresponding self-test alarms have been enabled under
Settings > Product Setup > User-Programmable
Self Tests
(not shown). The LEDs can be viewed on the front panel, so adding them to the annunciator is for illustrative
purposes only.
Figure 4-43: Annunciator editor and preview window
The three page layouts (3 × 4, 4 × 6, and 6 × 8) select the number of rows x columns of windows that appear in a page.
Annunciator window size and text size shrink as the number of annunciator windows in a page increases.