GE Multilin
L60 Line Phase Comparison Relay
3-35
3 HARDWARE
3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS
3
The ejector/inserter clips located at the top and at the bottom of each module, must be pulled simultaneously in order
to release the module for removal. Before performing this action,
control power must be removed from the relay
.
The original location of the module should be recorded to help ensure that the same or replacement module is inserted
into the correct slot.
2.
Remove the module cover screw.
3.
Remove the top cover by sliding it towards the rear and then lift it upwards.
4.
Set the Timing Selection Switches (Channel 1, Channel 2) to the desired timing modes (see description above).
5.
Replace the top cover and the cover screw.
6.
Re-insert the C37.94SM module Take care to ensure that the
correct
module type is inserted into the
correct
slot
position. The ejector/inserter clips located at the top and at the bottom of each module must be in the disengaged posi-
tion as the module is smoothly inserted into the slot. Once the clips have cleared the raised edge of the chassis,
engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted.
Figure 3–40: C37.94SM TIMING SELECTION SWITCH SETTING
Summary of Contents for L60
Page 2: ......
Page 4: ......
Page 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Page 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Page 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...