GE Multilin
L60 Line Phase Comparison Relay
3-11
3 HARDWARE
3.2 WIRING
3
The operation of voltage and current monitors is reflected with the corresponding FlexLogic™ operands (
Cont Op # Von
,
Cont
Op # Voff
,
Cont Op # Ion
, and
Cont Op # Ioff
) which can be used in protection, control and alarm logic. The typical application of
the voltage monitor is breaker trip circuit integrity monitoring; a typical application of the current monitor is seal-in of the
control command. Refer to the
Digital Elements
section of Chapter 5 for an example of how Form-A/SSR contacts can be
applied for breaker trip circuit integrity monitoring.
Relay contacts must be considered unsafe to touch when the unit is energized! If the relay contacts need to
be used for low voltage accessible applications, it is the customer’s responsibility to ensure proper insula-
tion levels!
USE OF FORM-A/SSR OUTPUTS IN HIGH IMPEDANCE CIRCUITS
For Form-A/SSR output contacts internally equipped with a voltage measuring cIrcuit across the contact, the circuit
has an impedance that can cause a problem when used in conjunction with external high input impedance monitor-
ing equipment such as modern relay test set trigger circuits. These monitoring circuits may continue to read the
Form-A contact as being closed after it has closed and subsequently opened, when measured as an impedance.
The solution to this problem is to use the voltage measuring trigger input of the relay test set, and connect the
Form-A contact through a voltage-dropping resistor to a DC voltage source. If the 48 V DC output of the power sup-
ply is used as a source, a 500
Ω
, 10 W resistor is appropriate. In this configuration, the voltage across either the
Form-A contact or the resistor can be used to monitor the state of the output.
Wherever a tilde “~” symbol appears, substitute with the slot position of the module; wherever a number
sign "#" appears, substitute the contact number
When current monitoring is used to seal-in the Form-A/SSR contact outputs, the FlexLogic™ operand driv-
ing the contact output should be given a reset delay of 10 ms to prevent damage of the output contact (in
situations when the element initiating the contact output is bouncing, at values in the region of the pickup
value).
Table 3–2: DIGITAL INPUT/OUTPUT MODULE ASSIGNMENTS
~6A MODULE
~6B MODULE
~6C MODULE
~6D MODULE
TERMINAL
ASSIGNMENT
OUTPUT OR
INPUT
TERMINAL
ASSIGNMENT
OUTPUT OR
INPUT
TERMINAL
ASSIGNMENT
OUTPUT
TERMINAL
ASSIGNMENT
OUTPUT
~1
Form-A
~1
Form-A
~1
Form-C
~
1a,
~
1c
2 Inputs
~2
Form-A
~2
Form-A
~2
Form-C
~
2a,
~
2c
2 Inputs
~3
Form-C
~3
Form-C
~3
Form-C
~
3a,
~
3c
2 Inputs
~4
Form-C
~4
Form-C
~4
Form-C
~
4a,
~
4c
2 Inputs
~5a, ~5c
2 Inputs
~5
Form-C
~5
Form-C
~
5a,
~
5c
2 Inputs
~6a, ~6c
2 Inputs
~6
Form-C
~6
Form-C
~
6a,
~
6c
2 Inputs
~7a, ~7c
2 Inputs
~7a, ~7c
2 Inputs
~7
Form-C
~
7a,
~
7c
2 Inputs
~8a, ~8c
2 Inputs
~8a, ~8c
2 Inputs
~8
Form-C
~
8a,
~
8c
2 Inputs
~6E MODULE
~6F MODULE
~6G MODULE
~6H MODULE
TERMINAL
ASSIGNMENT
OUTPUT OR
INPUT
TERMINAL
ASSIGNMENT
OUTPUT
TERMINAL
ASSIGNMENT
OUTPUT OR
INPUT
TERMINAL
ASSIGNMENT
OUTPUT OR
INPUT
~
1
Form-C
~
1
Fast Form-C
~
1
Form-A
~1
Form-A
~
2
Form-C
~
2
Fast Form-C
~
2
Form-A
~2
Form-A
~
3
Form-C
~
3
Fast Form-C
~
3
Form-A
~3
Form-A
~
4
Form-C
~
4
Fast Form-C
~
4
Form-A
~4
Form-A
~
5a,
~
5c
2 Inputs
~
5
Fast Form-C
~
5a,
~
5c
2 Inputs
~5
Form-A
~
6a,
~
6c
2 Inputs
~
6
Fast Form-C
~
6a,
~
6c
2 Inputs
~6
Form-A
~
7a,
~
7c
2 Inputs
~
7
Fast Form-C
~
7a,
~
7c
2 Inputs
~
7a,
~
7c
2 Inputs
~
8a,
~
8c
2 Inputs
~
8
Fast Form-C
~
8a,
~
8c
2 Inputs
~
8a,
~
8c
2 Inputs
WARNING
NOTE
NOTE
NOTE
Summary of Contents for L60
Page 2: ......
Page 4: ......
Page 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Page 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Page 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...