B-26
L60 Line Phase Comparison Relay
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
Phase Comparison Trip Scheme (Read/Write Grouped Setting)
60F0
87PC Function
0 to 1
---
1
F102
0 (Disabled)
60F1
87PC Channel Loss
0 to 500
ms
0.001
F001
0
60F2
87PC Block
0 to 65535
---
1
F300
0
60F3
87PC Target
0 to 2
---
1
F109
0 (Self-reset)
60F4
87PC Events
0 to 1
---
1
F102
0 (Disabled)
60F5
87PC Scheme Select
0 to 8
---
1
F149
1 (2TL-BL-DPC-3FC)
60F6
87PC Scheme Signal
0 to 1
---
1
F150
0 (MIXED I_2 - K*I_1)
60F7
87PC Signal Source
0 to 5
---
1
F167
0 (SRC 1)
60F8
87PC FDL Pickup
0.01 to 15
pu
0.01
F001
50
60FA
87PC FDH Pickup
0.01 to 15
pu
0.01
F001
75
60FB
87PC Mixed Signal K
0 to 0.25
---
0.01
F001
20
60FE
87PC Phase Delay Ch1
0 to 65.535
ms
0.001
F003
0
6100
87PC Phase Delay Ch2
0 to 65.535
ms
0.001
F003
0
6106
87PC Transient Pickup
0 to 65.535
s
0.001
F003
30
610A
87PC Asymmetry Channel 1
–20 to 20
ms
0.1
F004
0
610E
87PC Asymmetry Channel 2
–20 to 20
ms
0.1
F004
0
6110
87PC Stability Angle
40 to 140
degrees
10
F003
75
6112
87PC Transient Reset
0 to 65.535
s
0.001
F003
30
6113
87PC Received Volts Channel 1
0 to 125
V
0.1
F001
120
6114
87PC Received Volts Channel 2
0 to 125
V
0.1
F001
120
6115
87PC High-Speed Contact 1
0 to 64
---
1
F490
0
6116
87PC High-Speed Contact 2
0 to 64
---
1
F490
0
6117
87PC FDL AUX
0 to 65535
---
1
F300
0
6118
87PC FDH AUX
0 to 65535
---
1
F300
0
6119
87PC Reset Delay
0 to 200
ms
1
F001
30
CT Failure Detector (Read/Write Setting)
6120
CT Fail Function
0 to 1
---
1
F102
0 (Disabled)
6121
CT Fail Block
0 to 65535
---
1
F300
0
6122
CT Fail Current Source 1
0 to 5
---
1
F167
0 (SRC 1)
6123
CT Fail Current Pickup 1
0 to 2
pu
0.1
F001
2
6124
CT Fail Current Source 2
0 to 5
---
1
F167
1 (SRC 2)
6125
CT Fail Current Pickup 2
0 to 2
pu
0.1
F001
2
6126
CT Fail Voltage Source
0 to 5
---
1
F167
0 (SRC 1)
6127
CT Fail Voltage Pickup
0 to 2
pu
0.01
F001
20
6128
CT Fail Pickup Delay
0 to 65.535
s
0.001
F001
1000
6129
CT Fail Target
0 to 2
---
1
F109
0 (Self-reset)
612A
CT Fail Events
0 to 1
---
1
F102
0 (Disabled)
Continuous Monitor (Read/Write Setting)
6130
Continuous Monitor Function
0 to 1
---
1
F102
0 (Disabled)
6131
Continuous Monitor I OP
0 to 65535
---
1
F300
0
6132
Continuous Monitor I Supervision
0 to 65535
---
1
F300
0
6133
Continuous Monitor V OP
0 to 65535
---
1
F300
0
6134
Continuous Monitor V Supervision
0 to 65535
---
1
F300
0
6135
Continuous Monitor Target
0 to 2
---
1
F109
0 (Self-reset)
6136
Continuous Monitor Events
0 to 1
---
1
F102
0 (Disabled)
Negative Sequence Time Overcurrent (Read/Write Grouped Setting) (2 modules)
6300
Negative Sequence Time Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
6301
Negative Sequence Time Overcurrent 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
6302
Negative Sequence Time Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
6303
Negative Sequence Time Overcurrent 1 Curve
0 to 16
---
1
F103
0 (IEEE Mod Inv)
6304
Negative Sequence Time Overcurrent 1 Multiplier
0 to 600
---
0.01
F001
100
6305
Negative Sequence Time Overcurrent 1 Reset
0 to 1
---
1
F104
0 (Instantaneous)
6306
Negative Sequence Time Overcurrent 1 Block
0 to 65535
---
1
F300
0
Table B–9: MODBUS MEMORY MAP (Sheet 19 of 47)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for L60
Page 2: ......
Page 4: ......
Page 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Page 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Page 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...