GE Multilin
L60 Line Phase Comparison Relay
B-25
APPENDIX B
B.4 MEMORY MAPPING
B
5D10
...Repeated for Ground Time Overcurrent 2
5D20
...Repeated for Ground Time Overcurrent 3
5D30
...Repeated for Ground Time Overcurrent 4
5D40
...Repeated for Ground Time Overcurrent 5
5D50
...Repeated for Ground Time Overcurrent 6
Ground Instantaneous Overcurrent (Read/Write Grouped Setting) (12 modules)
5E00
Ground Instantaneous Overcurrent 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
5E01
Ground Instantaneous Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
5E02
Ground Instantaneous Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
5E03
Ground Instantaneous Overcurrent 1 Delay
0 to 600
s
0.01
F001
0
5E04
Ground Instantaneous Overcurrent 1 Reset Delay
0 to 600
s
0.01
F001
0
5E05
Ground Instantaneous Overcurrent 1 Block
0 to 65535
---
1
F300
0
5E06
Ground Instantaneous Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
5E07
Ground Instantaneous Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
5E08
Reserved (8 items)
0 to 1
---
1
F001
0
5E10
...Repeated for Ground Instantaneous Overcurrent 2
5E20
...Repeated for Ground Instantaneous Overcurrent 3
5E30
...Repeated for Ground Instantaneous Overcurrent 4
5E40
...Repeated for Ground Instantaneous Overcurrent 5
5E50
...Repeated for Ground Instantaneous Overcurrent 6
5E60
...Repeated for Ground Instantaneous Overcurrent 7
5E70
...Repeated for Ground Instantaneous Overcurrent 8
5E80
...Repeated for Ground Instantaneous Overcurrent 9
5E90
...Repeated for Ground Instantaneous Overcurrent 10
5EA0
...Repeated for Ground Instantaneous Overcurrent 11
5EB0
...Repeated for Ground Instantaneous Overcurrent 12
Setting Groups (Read/Write Setting)
5F80
Setting Group for Modbus Comms (0 means group 1)
0 to 5
---
1
F001
0
5F81
Setting Groups Block
0 to 65535
---
1
F300
0
5F82
FlexLogic to Activate Groups 2 through 6 (5 items)
0 to 65535
---
1
F300
0
5F89
Setting Group Function
0 to 1
---
1
F102
0 (Disabled)
5F8A
Setting Group Events
0 to 1
---
1
F102
0 (Disabled)
Setting Groups (Read Only)
5F8B
Current Setting Group
0 to 5
---
1
F001
0
Setting Group Names (Read/Write Setting)
5F8C
Setting Group 1 Name
---
---
---
F203
(none)
5494
Setting Group 2 Name
---
---
---
F203
(none)
5F9C
Setting Group 3 Name
---
---
---
F203
(none)
5FA4
Setting Group 4 Name
---
---
---
F203
(none)
5FAC
Setting Group 5 Name
---
---
---
F203
(none)
5FB4
Setting Group 6 Name
---
---
---
F203
(none)
Phase Comparison Open Breaker Keying (Read/Write Grouped Setting)
60E0
Open Breaker Keying
0 to 1
---
1
F102
0 (Disabled)
60E1
Breaker 1 Auxiliary Contact
0 to 65535
---
1
F300
0
60E2
Breaker 1 Supervision Element
0 to 65535
---
1
F300
0
60E3
Breaker 2 Auxiliary Contact
0 to 65535
---
1
F300
0
60E4
Breaker 2 Supervision Element
0 to 65535
---
1
F300
0
60E5
Weak-Infeed Keying
0 to 65535
---
1
F300
0
60E6
Supervision Element
0 to 65535
---
1
F300
0
60E7
Infeed Pickup Delay
0 to 50
s
0.001
F001
0
60E8
Infeed Reset Delay
0 to 50
s
0.001
F001
35
60E9
Open Breaker Keying Pickup Delay
0 to 50
s
0.001
F001
0
60EA
Open Breaker Keying Reset Delay
0 to 50
s
0.001
F001
0
Table B–9: MODBUS MEMORY MAP (Sheet 18 of 47)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for L60
Page 2: ......
Page 4: ......
Page 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Page 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Page 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...