B-18
L60 Line Phase Comparison Relay
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
40A6
Main UDP Port Number for the TFTP Protocol
1 to 65535
---
1
F001
69
40A7
Data Transfer UDP Port Numbers for the TFTP Protocol
(zero means “automatic”) (2 items)
0 to 65535
---
1
F001
0
40A9
DNP Unsolicited Responses Function
0 to 1
---
1
F102
0 (Disabled)
40AA
DNP Unsolicited Responses Timeout
0 to 60
s
1
F001
5
40AB
DNP Unsolicited Responses Max Retries
1 to 255
---
1
F001
10
40AC
DNP Unsolicited Responses Destination Address
0 to 65519
---
1
F001
1
40AD
Ethernet Operation Mode
0 to 1
---
1
F192
0 (Half-Duplex)
40AE
DNP Current Scale Factor
0 to 8
---
1
F194
2 (1)
40AF
DNP Voltage Scale Factor
0 to 8
---
1
F194
2 (1)
40B0
DNP Power Scale Factor
0 to 8
---
1
F194
2 (1)
40B1
DNP Energy Scale Factor
0 to 8
---
1
F194
2 (1)
40B2
DNP Other Scale Factor
0 to 8
---
1
F194
2 (1)
40B3
DNP Current Default Deadband
0 to 65535
---
1
F001
30000
40B4
DNP Voltage Default Deadband
0 to 65535
---
1
F001
30000
40B5
DNP Power Default Deadband
0 to 65535
---
1
F001
30000
40B6
DNP Energy Default Deadband
0 to 65535
---
1
F001
30000
40B7
DNP Other Default Deadband
0 to 65535
---
1
F001
30000
40B8
DNP IIN Time Sync Bit Period
1 to 10080
min
1
F001
1440
40B9
DNP Message Fragment Size
30 to 2048
---
1
F001
240
40BA
DNP Client Address 3
0 to 4294967295
---
1
F003
0
40BC
DNP Client Address 4
0 to 4294967295
---
1
F003
0
40BE
DNP Client Address 5
0 to 4294967295
---
1
F003
0
40C0
DNP Number of Paired Binary Output Control Points
0 to 16
---
1
F001
0
40C1
Reserved (31 items)
0 to 1
---
1
F001
0
40E0
TCP Port Number for the IEC 60870-5-104 Protocol
1 to 65535
---
1
F001
2404
40E1
IEC 60870-5-104 Protocol Function
0 to 1
---
1
F102
0 (Disabled)
40E2
IEC 60870-5-104 Protocol Common Address of ASDU
0 to 65535
---
1
F001
0
40E3
IEC 60870-5-104 Protocol Cyclic Data Trans. Period
1 to 65535
s
1
F001
60
40E4
IEC 60870-5-104 Current Default Threshold
0 to 65535
---
1
F001
30000
40E5
IEC 60870-5-104 Voltage Default Threshold
0 to 65535
---
1
F001
30000
40E6
IEC 60870-5-104 Power Default Threshold
0 to 65535
---
1
F001
30000
40E7
IEC 60870-5-104 Energy Default Threshold
0 to 65535
---
1
F001
30000
40E8
IEC 60870-5-104 Other Default Threshold
0 to 65535
---
1
F001
30000
40E9
IEC 60870-5-104 Client Address (5 items)
0 to 4294967295
---
1
F003
0
40FD
IEC 60870-5-104 Communications Reserved (60 items)
0 to 1
---
1
F001
0
4140
DNP Object 1 Default Variation
1 to 2
---
1
F001
2
4141
DNP Object 2 Default Variation
1 to 2
---
1
F001
2
4142
DNP Object 20 Default Variation
0 to 3
---
1
F523
0 (1)
4143
DNP Object 21 Default Variation
0 to 3
---
1
F524
0 (1)
4144
DNP Object 22 Default Variation
0 to 3
---
1
F523
0 (1)
4145
DNP Object 23 Default Variation
0 to 3
---
1
F523
0 (1)
4146
DNP Object 30 Default Variation
1 to 5
---
1
F001
1
4147
DNP Object 32 Default Variation
0 to 5
---
1
F525
0 (1)
Simple Network Time Protocol (Read/Write Setting)
4168
Simple Network Time Protocol (SNTP) Function
0 to 1
---
1
F102
0 (Disabled)
4169
Simple Network Time Protocol (SNTP) Server IP Address
0 to 4294967295
---
1
F003
0
416B
Simple Network Time Protocol (SNTP) UDP Port Number
1 to 65535
---
1
F001
123
Data Logger Commands (Read/Write Command)
4170
Data Logger Clear
0 to 1
---
1
F126
0 (No)
Data Logger (Read/Write Setting)
4181
Data Logger Channel Settings (16 items)
---
---
---
F600
0
4191
Data Logger Mode
0 to 1
---
1
F260
0 (continuous)
4192
Data Logger Trigger
0 to 65535
---
1
F300
0
Table B–9: MODBUS MEMORY MAP (Sheet 11 of 47)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for L60
Page 2: ......
Page 4: ......
Page 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Page 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Page 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...