GE Multilin
L60 Line Phase Comparison Relay
B-11
APPENDIX B
B.4 MEMORY MAPPING
B
Data Logger Actuals (Read Only)
1618
Data logger channel count
0 to 16
channel
1
F001
0
1619
Time of oldest available samples
0 to 4294967295
seconds
1
F050
0
161B
Time of newest available samples
0 to 4294967295
seconds
1
F050
0
161D
Data logger duration
0 to 999.9
days
0.1
F001
0
L60 Test Mode (Read Only)
1640
L60 Test Mode
0 to 1
---
1
F102
0 (Disabled)
L60 Test Mode (Read/Write Settings)
1641
L60 Trip Control Status
0 to 2
---
1
F134
2
1642
L60 Channel Status (4 items)
0 to 2
---
0.001
F134
2
Source Current (Read Only) (6 modules)
1800
Source 1 Phase A Current RMS
0 to 999999.999
A
0.001
F060
0
1802
Source 1 Phase B Current RMS
0 to 999999.999
A
0.001
F060
0
1804
Source 1 Phase C Current RMS
0 to 999999.999
A
0.001
F060
0
1806
Source 1 Neutral Current RMS
0 to 999999.999
A
0.001
F060
0
1808
Source 1 Phase A Current Magnitude
0 to 999999.999
A
0.001
F060
0
180A
Source 1 Phase A Current Angle
-359.9 to 0
degrees
0.1
F002
0
180B
Source 1 Phase B Current Magnitude
0 to 999999.999
A
0.001
F060
0
180D
Source 1 Phase B Current Angle
-359.9 to 0
degrees
0.1
F002
0
180E
Source 1 Phase C Current Magnitude
0 to 999999.999
A
0.001
F060
0
1810
Source 1 Phase C Current Angle
-359.9 to 0
degrees
0.1
F002
0
1811
Source 1 Neutral Current Magnitude
0 to 999999.999
A
0.001
F060
0
1813
Source 1 Neutral Current Angle
-359.9 to 0
degrees
0.1
F002
0
1814
Source 1 Ground Current RMS
0 to 999999.999
A
0.001
F060
0
1816
Source 1 Ground Current Magnitude
0 to 999999.999
A
0.001
F060
0
1818
Source 1 Ground Current Angle
-359.9 to 0
degrees
0.1
F002
0
1819
Source 1 Zero Sequence Current Magnitude
0 to 999999.999
A
0.001
F060
0
181B
Source 1 Zero Sequence Current Angle
-359.9 to 0
degrees
0.1
F002
0
181C
Source 1 Positive Sequence Current Magnitude
0 to 999999.999
A
0.001
F060
0
181E
Source 1 Positive Sequence Current Angle
-359.9 to 0
degrees
0.1
F002
0
181F
Source 1 Negative Sequence Current Magnitude
0 to 999999.999
A
0.001
F060
0
1821
Source 1 Negative Sequence Current Angle
-359.9 to 0
degrees
0.1
F002
0
1822
Source 1 Differential Ground Current Magnitude
0 to 999999.999
A
0.001
F060
0
1824
Source 1 Differential Ground Current Angle
-359.9 to 0
degrees
0.1
F002
0
1825
Reserved (27 items)
---
---
---
F001
0
1840
...Repeated for Source 2
1880
...Repeated for Source 3
18C0
...Repeated for Source 4
1900
...Repeated for Source 5
1940
...Repeated for Source 6
Source Voltage (Read Only) (6 modules)
1A00
Source 1 Phase AG Voltage RMS
0 to 999999.999
V
0.001
F060
0
1A02
Source 1 Phase BG Voltage RMS
0 to 999999.999
V
0.001
F060
0
1A04
Source 1 Phase CG Voltage RMS
0 to 999999.999
V
0.001
F060
0
1A06
Source 1 Phase AG Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A08
Source 1 Phase AG Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A09
Source 1 Phase BG Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A0B
Source 1 Phase BG Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A0C
Source 1 Phase CG Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A0E
Source 1 Phase CG Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A0F
Source 1 Phase AB or AC Voltage RMS
0 to 999999.999
V
0.001
F060
0
1A11
Source 1 Phase BC or BA Voltage RMS
0 to 999999.999
V
0.001
F060
0
1A13
Source 1 Phase CA or CB Voltage RMS
0 to 999999.999
V
0.001
F060
0
1A15
Source 1 Phase AB or AC Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
Table B–9: MODBUS MEMORY MAP (Sheet 4 of 47)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for L60
Page 2: ......
Page 4: ......
Page 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Page 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Page 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...