B-10
L60 Line Phase Comparison Relay
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
User Displays Actuals (Read Only)
1080
Formatted user-definable displays (16 items)
---
---
---
F200
(none)
Modbus User Map Actuals (Read Only)
1200
User Map Values (256 items)
0 to 65535
---
1
F001
0
Element Targets (Read Only)
14C0
Target Sequence
0 to 65535
---
1
F001
0
14C1
Number of Targets
0 to 65535
---
1
F001
0
Element Targets (Read/Write)
14C2
Target to Read
0 to 65535
---
1
F001
0
Element Targets (Read Only)
14C3
Target Message
---
---
---
F200
“.”
Digital Input/Output States (Read Only)
1500
Contact Input States (6 items)
0 to 65535
---
1
F500
0
1508
Virtual Input States (8 items)
0 to 65535
---
1
F500
0
1510
Contact Output States (4 items)
0 to 65535
---
1
F500
0
1518
Contact Output Current States (4 items)
0 to 65535
---
1
F500
0
1520
Contact Output Voltage States (4 items)
0 to 65535
---
1
F500
0
1528
Virtual Output States (6 items)
0 to 65535
---
1
F500
0
1530
Contact Output Detectors (4 items)
0 to 65535
---
1
F500
0
Remote Input/Output States (Read Only)
1540
Remote Device 1 States
0 to 65535
---
1
F500
0
1542
Remote Input States (4 items)
0 to 65535
---
1
F500
0
1550
Remote Devices Online
0 to 1
---
1
F126
0 (No)
Remote Device Status (Read Only) (16 modules)
1551
Remote Device 1 StNum
0 to 4294967295
---
1
F003
0
1553
Remote Device 1 SqNum
0 to 4294967295
---
1
F003
0
1555
...Repeated for Remote Device 2
1559
...Repeated for Remote Device 3
155D
...Repeated for Remote Device 4
1561
...Repeated for Remote Device 5
1565
...Repeated for Remote Device 6
1569
...Repeated for Remote Device 7
156D
...Repeated for Remote Device 8
1571
...Repeated for Remote Device 9
1575
...Repeated for Remote Device 10
1579
...Repeated for Remote Device 11
157D
...Repeated for Remote Device 12
1581
...Repeated for Remote Device 13
1585
...Repeated for Remote Device 14
1589
...Repeated for Remote Device 15
158D
...Repeated for Remote Device 16
Platform Direct Input/Output States (Read Only)
15C0
Direct input states (6 items)
0 to 65535
---
1
F500
0
15C8
Direct outputs average message return time 1
0 to 65535
ms
1
F001
0
15C9
Direct outputs average message return time 2
0 to 65535
ms
1
F001
0
15CA
Direct inputs/outputs unreturned message count - Ch. 1
0 to 65535
---
1
F001
0
15CB
Direct inputs/outputs unreturned message count - Ch. 2
0 to 65535
---
1
F001
0
15D0
Direct device states
0 to 65535
---
1
F500
0
15D1
Reserved
0 to 65535
---
1
F001
0
15D2
Direct inputs/outputs CRC fail count 1
0 to 65535
---
1
F001
0
15D3
Direct inputs/outputs CRC fail count 2
0 to 65535
---
1
F001
0
Ethernet Fibre Channel Status (Read/Write)
1610
Ethernet primary fibre channel status
0 to 2
---
1
F134
0 (Fail)
1611
Ethernet secondary fibre channel status
0 to 2
---
1
F134
0 (Fail)
Table B–9: MODBUS MEMORY MAP (Sheet 3 of 47)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for L60
Page 2: ......
Page 4: ......
Page 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Page 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Page 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...