GE Multilin
L60 Line Phase Comparison Relay
2-15
2 PRODUCT DESCRIPTION
2.2 SPECIFICATIONS
2
CONTROL POWER EXTERNAL OUTPUT
(FOR DRY CONTACT INPUT)
Capacity:
100 mA DC at 48 V DC
Isolation:
±300 Vpk
REMOTE OUTPUTS (IEC 61850 GSSE/GOOSE)
Standard output points: 32
User output points:
32
DCMA OUTPUTS
Range:
–1 to 1 mA, 0 to 1 mA, 4 to 20 mA
Max. load resistance:
12 k
Ω
for –1 to 1 mA range
12 k
Ω
for 0 to 1 mA range
600
Ω
for 4 to 20 mA range
Accuracy:
±0.75% of full-scale for 0 to 1 mA range
±0.5% of full-scale for –1 to 1 mA range
±0.75% of full-scale for 0 to 20 mA range
99% Settling time to a step change: 100 ms
Isolation:
1.5 kV
Driving signal:
any FlexAnalog quantity
Upper and lower limit for the driving signal: –90 to 90 pu in steps of
0.001
2.2.8 COMMUNICATIONS
RS232
Front port:
19.2 kbps, Modbus
®
RTU
RS485
1 or 2 rear ports:
Up to 115 kbps, Modbus
®
RTU, isolated
together at 36 Vpk
Typical distance:
1200 m
Isolation:
2 kV
ETHERNET (FIBER)
ETHERNET (COPPER)
Modes:
10 MB, 10/100 MB (auto-detect)
Connector:
RJ45
SNTP clock synchronization error: <10 ms (typical)
PARAMETER
FIBER TYPE
10MB MULTI-
MODE
100MB MULTI-
MODE
100MB SINGLE-
MODE
Wavelength
820 nm
1310 nm
1310 nm
Connector
ST
ST
SC
Transmit power
–20 dBm
–20 dBm
–15 dBm
Receiver sensitivity
–30 dBm
–30 dBm
–30 dBm
Power budget
10 dB
10 dB
15 dB
Maximum input
power
–7.6 dBm
–14 dBm
–7 dBm
Typical distance
1.65 km
2 km
15 km
Duplex
full/half
full/half
full/half
Redundancy
yes
yes
yes
Summary of Contents for L60
Page 2: ......
Page 4: ......
Page 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Page 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Page 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...