9-2
L60 Line Phase Comparison Relay
GE Multilin
9.1 PHASE COMPARISON ELEMENT 87PC
9 APPLICATION OF SETTINGS
9
and ground directional. The user must be aware that auxiliary element assigned with FDL AUX does not provide any trip-
ping function, but only starts the carrier to send pulses to remote terminal and allow the coincidence detector to make trip/
block decisions.
87PC FDH AUX:
This setting is provided for cases (similar to FDL AUX) when sensitivity of the built-in FDH operating on the I_2 – K*I_1
quantity is not sufficient. FDH AUX is connected in parallel with the built-in FDH fault detector and is intended to be
assigned with elements such as distance, negative-sequence overvoltage and overcurrent, and ground directional. FDH
(along with FDH AUX) provides arming action for phase comparison trip decisions, allowing trips only when the coincidence
detector detects internal fault conditions and FDL (or FDL AUX) operates.
87PC SYMMETRY CH 1(2):
This setting is used to make the local squared signal and the received signal from the remote terminal symmetrical. To set
it properly, keying of the remote transmitter and an oscilloscope are required. If the received signal is ideally symmetrical
with respect to the "Mark" and "Space" signals, a value of 0 ms (set as default) should be used. If for example, measured
length of the "Mark" is longer than "Space" for 4.0 ms, setting "–2.0 ms" to be entered. If the measured length of the "Mark"
is shorter than "Space" for 3.0 ms, setting "+1.5 ms" is to be entered. As sum of "Mark" and "Space" signals equals the
length of the power cycle, corresponding scaling of the signals should be made for off nominal system frequencies.
Negative setting time is needed if the receiver elongates the received signal and positive setting time is needed if the
receiver shortens the signal.
The L60 allows the customer to check and set channel symmetry without using an oscilloscope, by means of FlexLogic™
operands and applying the corresponding current to the relays which in turn key the PLC and consequently measure
"Mark" and "Space" signals on the oscillography. Moving cursors and measuring an average from a few points time, the
user can determine and enter setting.
87PC PHASE DELAY CH1(2):
This setting is made in the field to be equal to the sum of three delays; symmetry adjustment, propagation time of the line
and receiver. Different methods can be used.
The L60 allows the customer to check and set phase delay without using an oscilloscope and by means of FlexLogic™
operands and applying the corresponding current to both relays. Oscillography shows the time difference (including PLC
delay and line propagation time) between local and remote signals. Moving cursors and measuring an average from a few
points time, the user can determine and apply the proper setting
87PC STABILITY ANGLE:
Stability angle setting must accommodate the security requirements for the external fault and dependability requirements
for the internal fault. Default value 3 ms corresponds to about 65 degrees of blocking zone for a 60 Hz system. It overrides
sources angular shift resulting from load, charging current, CT errors, etc.
The stability angle js can be estimated as follows:
φ
s =
φ
load +
φ
capac +
φ
ct
where:
φ
load is a sources angular shift phase between the line terminal at maximum expected load, expressed in electri-
cal degrees.
φ
capac is the capacitive current compensation angle evaluated as
φ
capac = arctan (Icapac / I
FDH
) expressed in
electrical degrees, where Icapac is a line capacitive current, I
FDH
-setting of FDH (fault detector high).
φ
ct is the CTs error and saturation compensation angle and can be adopted as equal 10° for most cases unless
there is a special consideration or concern. For such cases
φ
ct can be increased up to 20°.
87PC TRANS BLOCK PICKUP:
This setting is used to increase security during and after clearing of an external fault and to prevent false tripping during
current reversals. The setting should be higher than the time difference in operation between FDH and output from the
coincidence discriminator. A setting 10-30 ms gives sufficient security for most conditions.
87PC TRANS BLOCK RESET:
This setting is used to reset transient blocking and allow tripping. According to local conditions, setting should be consid-
ered as the sum of protection operating time and breaker opening time of the adjacent line and minus the Transient Pickup
value to override uncertainty during clearing external faults. The faster the fault clearing at the adjacent line, the lower set-
ting could be applied.
Summary of Contents for L60
Page 2: ......
Page 4: ......
Page 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Page 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Page 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...