GE Multilin
L60 Line Phase Comparison Relay
7-3
7 COMMANDS AND TARGETS
7.2 TARGETS
7
7.2TARGETS
7.2.1 TARGETS MENU
The status of any active targets will be displayed in the Targets menu. If no targets are active, the display will read
No
Active Targets
:
7.2.2 TARGET MESSAGES
When there are no active targets, the first target to become active will cause the display to immediately default to that mes-
sage. If there are active targets and the user is navigating through other messages, and when the default message timer
times out (i.e. the keypad has not been used for a determined period of time), the display will again default back to the tar-
get message.
The range of variables for the target messages is described below. Phase information will be included if applicable. If a tar-
get message status changes, the status with the highest priority will be displayed.
If a self test error is detected, a message appears indicating the cause of the error. For example
UNIT NOT PROGRAMMED
indicates that the minimal relay settings have not been programmed.
7.2.3 RELAY SELF-TESTS
The relay performs a number of self-test diagnostic checks to ensure device integrity. The two types of self-tests (major and
minor) are listed in the tables below. When either type of self-test error occurs, the Trouble LED Indicator will turn on and a
target message displayed. All errors record an event in the event recorder. Latched errors can be cleared by pressing the
RESET key, providing the condition is no longer present.
Major self-test errors also result in the following:
•
the critical fail relay on the power supply module is de-energized
•
all other output relays are de-energized and are prevented from further operation
•
the faceplate In Service LED indicator is turned off
•
a RELAY OUT OF SERVICE event is recorded
Most of the minor self-test errors can be disabled. Refer to the settings in the User-Programmable Self-Tests section in
Chapter 5 for additional details.
TARGETS
MESSAGE
DIGITAL ELEMENT 1:
LATCHED
Displayed only if targets for this element are active.
Example shown.
MESSAGE
DIGITAL ELEMENT 48:
LATCHED
Displayed only if targets for this element are active.
Example shown.
MESSAGE
↓
↓
Table 7–1: TARGET MESSAGE PRIORITY STATUS
PRIORITY
ACTIVE STATUS
DESCRIPTION
1
OP
element operated and still picked up
2
PKP
element picked up and timed out
3
LATCHED
element had operated but has dropped out
Summary of Contents for L60
Page 2: ......
Page 4: ......
Page 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Page 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Page 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...