GE Multilin
L60 Line Phase Comparison Relay
5-211
5 SETTINGS
5.7 INPUTS/OUTPUTS
5
•
Setting
REMOTE IN 1 DEFAULT STATE
to “Latest/On” freezes the input in case of lost communications. If the latest state is
not known, such as after relay power-up but before the first communication exchange, the input will default to Logic 1.
When communication resumes, the input becomes fully operational.
•
Setting
REMOTE IN 1 DEFAULT STATE
to “Latest/Off” freezes the input in case of lost communications. If the latest state is
not known, such as after relay power-up but before the first communication exchange, the input will default to Logic 0.
When communication resumes, the input becomes fully operational.
For additional information on GSSE/GOOOSE messaging, refer to the
Remote Devices
section in this chap-
ter.
5.7.7 REMOTE OUTPUTS
a) DNA BIT PAIRS
PATH: SETTINGS
INPUTS/OUTPUTS
REMOTE OUTPUTS DNA BIT PAIRS REMOTE OUPUTS DNA- 1(32) BIT PAIR
Remote outputs (1 to 32) are FlexLogic™ operands inserted into GSSE/GOOSE messages that are transmitted to remote
devices on a LAN. Each digital point in the message must be programmed to carry the state of a specific FlexLogic™ oper-
and. The above operand setting represents a specific DNA function (as shown in the following table) to be transmitted.
b) USERST BIT PAIRS
PATH: SETTINGS
INPUTS/OUTPUTS
REMOTE OUTPUTS UserSt BIT PAIRS REMOTE OUTPUTS UserSt- 1(32) BIT PAIR
Remote outputs 1 to 32 originate as GSSE/GOOSE messages to be transmitted to remote devices. Each digital point in the
message must be programmed to carry the state of a specific FlexLogic™ operand. The setting above is used to select the
operand which represents a specific UserSt function (as selected by the user) to be transmitted.
The following setting represents the time between sending GSSE/GOOSE messages when there has been no change of
state of any selected digital point. This setting is located in the
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTO-
COL
GSSE/GOOSE CONFIGURATION
settings menu.
The following setting determines whether remote input/output data is transported using IEC 61850 GSSE or IEC 61850
GOOSE messages. If GOOSE is selected, the VLAN and APPID settings should be set accordingly. If GSSE is selected,
the VLAN and APPID settings are not relevant. This setting is located in the
PRODUCT SETUP
COMMUNICATIONS
IEC
61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
menu.
For more information on GSSE/GOOSE messaging, refer to
Remote Inputs/Outputs Overview
in the
Remote Devices
section.
REMOTE OUTPUTS
DNA- 1 BIT PAIR
DNA- 1 OPERAND:
Off
Range: FlexLogic™ operand
MESSAGE
DNA- 1 EVENTS:
Disabled
Range: Disabled, Enabled
Table 5–24: IEC 61850 DNA ASSIGNMENTS
DNA
IEC 61850 DEFINITION
FLEXLOGIC™ OPERAND
1
Test
IEC 61850 TEST MODE
2
ConfRev
IEC 61850 CONF REV
REMOTE OUTPUTS
UserSt- 1 BIT PAIR
UserSt- 1 OPERAND:
Off
Range: FlexLogic™ operand
MESSAGE
UserSt- 1 EVENTS:
Disabled
Range: Disabled, Enabled
DEFAULT GSSE/GOOSE
UPDATE TIME: 60 s
Range: 1 to 60 s in steps of 1
REMOTE I/O TRANSFER
METHOD: GSSE
Range: GOOSE, GSSE, None
NOTE
NOTE
Summary of Contents for L60
Page 2: ......
Page 4: ......
Page 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Page 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Page 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...