ADDENDUM
This Addendum contains information that relates to the L60 Line Phase Comparison Relay relay, version 4.9x. This
addendum lists a number of information items that appear in the instruction manual GEK-113209A (revision
M2
) but are
not included in the current L60 operations.
The following functions/items are not yet available with the current version of the L60 relay:
• N/A
Version 4.0x and higher releases of the L60 relay includes new hardware (CPU and CT/VT modules).
• The new CPU modules are specified with the following order codes: 9E, 9G, 9H, 9J, 9K, 9L, 9M, 9N, 9P, and 9R.
• The new CT/VT modules are specified with the following order codes: 8F, 8H, 8P.
The following table maps the relationship between the old CPU and CT/VT modules to the newer versions:
The new CT/VT modules can only be used with the new CPUs (9E, 9G, 9H, 9J, 9K, 9L, 9M, 9N, 9P, 9R), and the old CT/
VT modules can only be used with the old CPU modules (9A, 9C, 9D). To prevent any hardware mismatches, the new
CPU and CT/VT modules have blue labels and a warning sticker stating
“Attn.: Ensure CPU and DSP module label
colors are the same!”
. In the event that there is a mismatch between the CPU and CT/VT module, the relay will not
function and a
DSP ERROR
or
HARDWARE MISMATCH
error will be displayed.
MODULE
OLD
NEW
DESCRIPTION
CPU
9A
9E
RS485 and RS485 (Modbus RTU, DNP)
9C
9G
RS485 and 10Base-F (Ethernet, Modbus TCP/IP, DNP)
9D
9H
RS485 and redundant 10Base-F (Ethernet, Modbus TCP/IP, DNP)
--
9J
RS485 and multi-mode ST 100Base-FX
--
9K
RS485 and multi-mode ST redundant 100Base-FX
--
9L
RS485 and single mode SC 100Base-FX
--
9M
RS485 and single mode SC redundant 100Base-FX
--
9N
RS485 and 10/100Base-T
--
9P
RS485 and single mode ST 100Base-FX
--
9R
RS485 and single mode ST redundant 100Base-FX
CT/VT
8A
8F
Standard 4CT/4VT
8C
8H
Standard 8CT
N/A
8P
Special 4CT module with communications channel for L60
GE Multilin
215 Anderson Avenue, Markham, Ontario
Canada L6E 1B3
Tel: (905) 294-6222 Fax: (905) 201-2098
Internet:
http://www.GEindustrial.com/multilin
Addendum
Summary of Contents for L60
Page 2: ......
Page 4: ......
Page 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Page 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Page 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...