
5-192
L60 Line Phase Comparison Relay
GE Multilin
5.6 CONTROL ELEMENTS
5 SETTINGS
5
The autoreclose scheme is intended for use on transmission lines with circuit breakers operated in both the single pole and
three pole modes, in one or two breaker arrangements. The autoreclose scheme provides four programs with different
operating cycles, depending on the fault type. Each of the four programs can be set to trigger up to two reclosing attempts.
The second attempt always performs three pole reclosing and has an independent dead time delay.
When used in two breaker applications, the reclosing sequence is selectable. The reclose signal can be sent to one
selected breaker only, to both breakers simultaneously or to both breakers in sequence (one breaker first and then, after a
delay to check that the reclose was successful, to the second breaker). When reclosing in sequence, the first breaker
should reclose with either the 1-Pole or 3-Pole dead time according to the fault type and reclose mode; the second breaker
should follow the successful reclosure of the first breaker. When reclosing simultaneously, for the first shot both breakers
should reclose with either the 1-Pole or 3-Pole dead time, according to the fault type and the reclose mode.
The signal used to initiate the autoreclose scheme is the trip output from protection. This signal can be single pole tripping
for single phase faults and three phase tripping for multiphase faults. The autoreclose scheme has five operating states.
MESSAGE
AR BKR CLOSED:
Off
Range: FlexLogic™ operand
MESSAGE
AR BLOCK:
Off
Range: FlexLogic™ operand
MESSAGE
AR PAUSE:
Off
Range: FlexLogic™ operand
MESSAGE
AR INCOMPLETE SEQ
TIME: 5.00 s
Range: 0 to 655.35 s in steps of 0.01
MESSAGE
AR BLOCK BKR2:
Off
Range: FlexLogic™ operand
MESSAGE
AR CLOSE TIME BKR2:
0.10 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR TRANSFER 1 TO 2:
No
Range: Yes, No
MESSAGE
AR TRANSFER 2 TO 1:
No
Range: Yes, No
MESSAGE
AR BKR1 FAIL OPTION:
Continue
Range: Continue, Lockout
MESSAGE
AR BKR2 FAIL OPTION:
Continue
Range: Continue, Lockout
MESSAGE
AR 1-P DEAD TIME:
1.00 s
Range: 0 to 655.35 s in steps of 0.01
MESSAGE
AR BKR SEQUENCE:
1-2
Range: 1, 2, 1&2, 1–2, 2–1
MESSAGE
AR TRANSFER TIME:
4.00 s
Range: 0 to 655.35 s in steps of 0.01
MESSAGE
AR EVENT:
Disabled
Range: Enabled, Disabled
STATE
CHARACTERISTICS
Enabled
Scheme is permitted to operate
Disabled
Scheme is not permitted to operate
Reset
Scheme is permitted to operate and shot count is reset to 0
Reclose In Progress
Scheme has been initiated but the reclose cycle is not finished (successful or not)
Lockout
Scheme is not permitted to operate until reset received
Summary of Contents for L60
Page 2: ......
Page 4: ......
Page 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Page 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Page 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...