5-184
L60 Line Phase Comparison Relay
GE Multilin
5.6 CONTROL ELEMENTS
5 SETTINGS
5
•
CT FAIL 3I0 INPUT 2 PICKUP
: This setting is used to select the pickup value for 3I_0 for the Input 2 (different CT
input) of the relay.
•
CT FAIL 3V0 INPUT:
This setting is used to select the source for the voltage.
•
CT FAIL 3V0 INPUT PICKUP:
This setting is used to select the pickup value for 3V_0 source.
•
CT FAIL PICKUP DELAY:
This setting is used to select the pickup delay of the element.
Figure 5–107: CT FAILURE DETECTOR SCHEME LOGIC
CT FAIL FUNCTION:
CT FAIL BLOCK:
CT FAIL 3IO INPUT1:
CT FAIL 3IO INPUT1 PKP:
CT FAIL 3VO INPUT:
CT FAIL 3VO INPUT:
CT FAIL 3IO INPUT2:
CT FAIL 3IO INPUT2 PKP:
CT FAIL PICKUP DELAY:
AND
OR
SETTING
Enabled=1
Disabled=0
SETTING
SETTING
SETTING
SETTING
SETTING
SETTING
SETTING
SETTING
Off=0
SRC1
RUN 3IO > PICKUP
3IO > PICKUP
3VO > PICKUP
SRC1
RUN
SRC2
RUN
FLEXLOGIC OPERANDS
CT FAIL OP
CT FAIL PKP
827048A6.CDR
0