5-183
5 SETTINGS
5.6 CONTROL ELEMENTS
5
d) CT FAILURE
PATH: SETTINGS
CONTROL ELEMENTS
MONITORING ELEMENTS
CT FAILURE DETECTOR
The CT Failure function is designed to detect problems with the system current transformers used to supply current to the
relay. This logic detects the presence of a zero sequence current at the supervised source of current without a simulta-
neous zero-sequence current at another source, zero-sequence voltage or some protection element condition.
The CT Failure logic (see figure below) is based on the presence of the zero sequence current in the supervised CT source
and absence of one of three or all three conditions as follows:
1.
Zero sequence current at different source current (may be different set of CTs or different CT core of the same CT).
2.
Zero sequence voltage at the assigned source.
3.
Appropriate protection element or remote signal.
The CT Failure settings are described below.
•
CT FAIL FUNCTION:
This setting is used to Enable/Disable operation of the element.
•
CT FAIL BLOCK:
This setting is used to select a FlexLogic™ operand that blocks operation of the element during
some conditions (i.e. open pole in process of the single pole tripping-reclosing) when CT Fail should be blocked.
Remote signals representing operation of some remote current protection elements via communication channel or
local ones can be chosen as well.
•
CT FAIL 3I0 INPUT 1:
This setting is used to select the source for the current for Input 1. Most important protection
element of the relay should be assigned to the same source.
•
CT FAIL 3I0 INPUT 1 PICKUP:
This setting is used to select the pickup value for 3I_0 for Input 1 (main supervised CT
source) of the relay.
•
CT FAIL 3I0 INPUT 2
: This setting is used to select the source for the current for Input 2. Input 2 should use different
set of CTs or different CT core of the same CT. Against absence at Input 2 CT source (if exists), 3I_0 current logic is
built.
CT FAILURE
DETECTOR
CT FAIL FUNCTION:
Disabled
Range: Disabled, Enabled
MESSAGE
CT FAIL BLOCK:
Off
Range: FlexLogic™ operand
MESSAGE
CT FAIL 3I0 INPUT 1:
SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
CT FAIL 3I0 INPUT 1
PKP: 0.20 pu
Range: 0.00 to 2.00 pu in steps of 0.01
MESSAGE
CT FAIL 3I0 INPUT 2:
SRC 2
Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
CT FAIL 3I0 INPUT 2
PKP: 0.20 pu
Range: 0.00 to 2.00 pu in steps of 0.01
MESSAGE
CT FAIL 3V0 INPUT:
SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
CT FAIL 3V0 INPUT
PKP: 0.20 pu
Range: 0.00 to 2.00 pu in steps of 0.01
MESSAGE
CT FAIL PICKUP
DELAY: 1.000 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
CT FAIL TARGET:
Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
CT FAIL EVENTS:
Disabled
Range: Disabled, Enabled
Summary of Contents for L60
Page 2: ......
Page 4: ......
Page 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Page 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Page 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...