GE Multilin
L60 Line Phase Comparison Relay
5-177
5 SETTINGS
5.6 CONTROL ELEMENTS
5
5.6.8 MONITORING ELEMENTS
a) MAIN MENU
PATH: SETTINGS
CONTROL ELEMENTS
MONITORING ELEMENTS
b) BREAKER ARCING CURRENT
PATH: SETTINGS
CONTROL ELEMENTS
MONITORING ELEMENTS BREAKER 1(2) ARCING CURRENT
MONITORING
ELEMENTS
BREAKER 1
ARCING CURRENT
See below.
MESSAGE
BREAKER 2
ARCING CURRENT
See below.
MESSAGE
BREAKER
FLASHOVER 1
MESSAGE
BREAKER
FLASHOVER 2
MESSAGE
CT FAILURE
DETECTOR
MESSAGE
VT FUSE FAILURE 1
MESSAGE
VT FUSE FAILURE 2
MESSAGE
OPEN POLE
BREAKER 1
ARCING CURRENT
BKR 1 ARC AMP
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
BKR 1 ARC AMP
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
BKR 1 ARC AMP INT-A:
Off
Range: FlexLogic™ operand
MESSAGE
BKR 1 ARC AMP INT-B:
Off
Range: FlexLogic™ operand
MESSAGE
BKR 1 ARC AMP INT-C:
Off
Range: FlexLogic™ operand
MESSAGE
BKR 1 ARC AMP
DELAY: 0.000
s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
BKR 1 ARC AMP LIMIT:
1000 kA2-cyc
Range: 0 to 50000 kA
2
-cycle in steps of 1
MESSAGE
BKR 1 ARC AMP BLOCK:
Off
Range: FlexLogic™ operand
MESSAGE
BKR 1 ARC AMP
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
BKR 1 ARC AMP
EVENTS: Disabled
Range: Disabled, Enabled
Summary of Contents for L60
Page 2: ......
Page 4: ......
Page 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Page 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Page 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...