5-172
L60 Line Phase Comparison Relay
GE Multilin
5.6 CONTROL ELEMENTS
5 SETTINGS
5
5.6.6 DIGITAL ELEMENTS
PATH: SETTINGS
CONTROL ELEMENTS
DIGITAL ELEMENTS DIGITAL ELEMENT 1(48)
There are 48 identical digital elements available, numbered 1 to 48. A digital element can monitor any FlexLogic™ operand
and present a target message and/or enable events recording depending on the output operand state. The digital element
settings include a name which will be referenced in any target message, a blocking input from any selected FlexLogic™
operand, and a timer for pickup and reset delays for the output operand.
•
DIGITAL ELEMENT 1 INPUT:
Selects a FlexLogic™ operand to be monitored by the digital element.
•
DIGITAL ELEMENT 1 PICKUP DELAY:
Sets the time delay to pickup. If a pickup delay is not required, set to "0".
•
DIGITAL ELEMENT 1 RESET DELAY:
Sets the time delay to reset. If a reset delay is not required, set to “0”.
•
DIGITAL ELEMENT 1 PICKUP LED
: This setting enables or disabled the digital element pickup LED. When set to
“Disabled”, the operation of the pickup LED is blocked.
Figure 5–100: DIGITAL ELEMENT SCHEME LOGIC
CIRCUIT MONITORING APPLICATIONS:
Some versions of the digital input modules include an active voltage monitor circuit connected across Form-A contacts. The
voltage monitor circuit limits the trickle current through the output circuit (see technical specifications for Form-A).
DIGITAL ELEMENT 1
DIGITAL ELEMENT 1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
DIG ELEM 1 NAME:
Dig Element 1
Range: 16 alphanumeric characters
MESSAGE
DIG ELEM 1 INPUT:
Off
Range: FlexLogic™ operand
MESSAGE
DIG ELEM 1 PICKUP
DELAY: 0.000
s
Range: 0.000 to 999999.999 s in steps of 0.001
MESSAGE
DIG ELEM 1 RESET
DELAY: 0.000
s
Range: 0.000 to 999999.999 s in steps of 0.001
MESSAGE
DIG ELEMENT 1
PICKUP LED: Enabled
Range: Disabled, Enabled
MESSAGE
DIG ELEM 1 BLOCK:
Off
Range: FlexLogic™ operand
MESSAGE
DIGITAL ELEMENT 1
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
DIGITAL ELEMENT 1
EVENTS: Disabled
Range: Disabled, Enabled
S
ETT
I
NG
DIGITAL ELEMENT 01
FUNCTION:
Disabled = 0
Enabled = 1
DIGITAL ELEMENT 01
BLOCK:
Off = 0
FLEXLOG
I
C OPE
R
AND
S
DIG ELEM 01 DPO
DIG ELEM 01 PKP
S
ETT
I
NG
827042A1.VSD
DIGITAL ELEMENT 01
INPUT:
Off = 0
S
ETT
I
NG
INPUT = 1
RUN
t
PKP
t
R
S
T
DIGITAL ELEMENT 01
PICKUP DELAY:
S
ETT
I
NG
S
DIGITAL ELEMENT 01
RESET DELAY:
AND
S
ETT
I
NG
DIGITAL ELEMENT 01
NAME:
DIG ELEM 01 OP
Summary of Contents for L60
Page 2: ......
Page 4: ......
Page 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Page 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Page 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...