5-130
L60 Line Phase Comparison Relay
GE Multilin
5.5 GROUPED ELEMENTS
5 SETTINGS
5
•
Transformation errors of current transformers (CTs) during double-line and three-phase faults.
•
Switch-off transients during double-line and three-phase faults.
The positive-sequence restraint must be considered when testing for pickup accuracy and response time (multiple of
pickup). The operating quantity depends on the way the test currents are injected into the relay (single-phase injection:
I
op
= (1 –
K
)
×
I
injected
; three-phase pure zero-sequence injection:
I
op
= 3
×
I
injected
).
The positive-sequence restraint is removed for low currents. If the positive-sequence current is below 0.8 pu, the restraint is
removed by changing the constant
K
to zero. This facilitates better response to high-resistance faults when the unbalance
is very small and there is no danger of excessive CT errors as the current is low.
The
directional unit
uses the zero-sequence current (I_0) or ground current (IG) for fault direction discrimination and may
be programmed to use either zero-sequence voltage (“Calculated V0” or “Measured VX”), ground current (IG), or both for
polarizing. The following tables define the neutral directional overcurrent element.
where:
,
,
ECA = element characteristic angle and IG = ground current
When
NEUTRAL DIR OC1 POL VOLT
is set to “Measured VX”, one-third of this voltage is used in place of V_0. The following
figure explains the usage of the voltage polarized directional unit of the element.
The figure below shows the voltage-polarized phase angle comparator characteristics for a phase A to ground fault, with:
ECA = 90° (element characteristic angle = centerline of operating characteristic)
FWD LA = 80° (forward limit angle = the ± angular limit with the ECA for operation)
REV LA = 80° (reverse limit angle = the ± angular limit with the ECA for operation)
The element incorporates a current reversal logic: if the reverse direction is indicated for at least 1.25 of a power system
cycle, the prospective forward indication will be delayed by 1.5 of a power system cycle. The element is designed to emu-
late an electromechanical directional device. Larger operating and polarizing signals will result in faster directional discrimi-
nation bringing more security to the element operation.
The forward-looking function is designed to be more secure as compared to the reverse-looking function, and therefore,
should be used for the tripping direction. The reverse-looking function is designed to be faster as compared to the forward-
looking function and should be used for the blocking direction. This allows for better protection coordination.
Table 5–20: QUANTITIES FOR "CALCULATED 3I0" CONFIGURATION
DIRECTIONAL UNIT
OVERCURRENT UNIT
POLARIZING MODE
DIRECTION
COMPARED PHASORS
Voltage
Forward
–V_0 + Z_offset
×
I_0
I_0
×
1
∠
ECA
I
op
= 3
×
(|I_0| – K
×
|I_1|) if |I
1
| > 0.8 pu
I
op
= 3
×
(|I_0|) if |I
1
|
≤
0.8 pu
Reverse
–V_0 + Z_offset
×
I_0
–I_0
×
1
∠
ECA
Current
Forward
IG
I_0
Reverse
IG
–I_0
Dual
Forward
–V_0 + Z_offset
×
I_0
I_0
×
1
∠
ECA
or
IG
I_0
Reverse
–V_0 + Z_offset
×
I_0
–I_0
×
1
∠
ECA
or
IG
–I_0
Table 5–21: QUANTITIES FOR "MEASURED IG" CONFIGURATION
DIRECTIONAL UNIT
OVERCURRENT UNIT
POLARIZING MODE
DIRECTION
COMPARED PHASORS
Voltage
Forward
–V_0 + Z_offset
×
IG/3
IG
×
1
∠
ECA
I
op
= |IG|
Reverse
–V_0 + Z_offset
×
IG/3
–IG
×
1
∠
ECA
V_0
1
3
---
VAG VBG VCG
+
+
(
)
zero sequence voltage
=
=
I_0
1
3
---
IN
1
3
---
IA IB IC
+
+
(
)
zero sequence current
=
=
=
Summary of Contents for L60
Page 2: ......
Page 4: ......
Page 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Page 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Page 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...