5-114
L60 Line Phase Comparison Relay
GE Multilin
5.5 GROUPED ELEMENTS
5 SETTINGS
5
5.5.7 LOAD ENCROACHMENT
PATH: SETTINGS
GROUPED ELEMENTS SETTING GROUP 1(6)
LOAD ENCROACHMENT
The Load Encroachment element responds to the positive-sequence voltage and current and applies a characteristic
shown in the figure below.
Figure 5–64: LOAD ENCROACHMENT CHARACTERISTIC
The element operates if the positive-sequence voltage is above a settable level and asserts its output signal that can be
used to block selected protection elements such as distance or phase overcurrent. The following figure shows an effect of
the Load Encroachment characteristics used to block the Quad distance element.
LOAD ENCROACHMENT
LOAD ENCROACHMENT
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
LOAD ENCROACHMENT
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
LOAD ENCROACHMENT
MIN VOLT: 0.250 pu
Range: 0.000 to 3.000 pu in steps of 0.001
MESSAGE
LOAD ENCROACHMENT
REACH: 1.00
Ω
Range: 0.02 to 250.00 ohms in steps of 0.01
MESSAGE
LOAD ENCROACHMENT
ANGLE: 30°
Range: 5 to 50° in steps of 1
MESSAGE
LOAD ENCROACHMENT
PKP DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
LOAD ENCROACHMENT
RST DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
LOAD ENCRMNT BLK:
Off
Range: Flexlogic™ operand
MESSAGE
LOAD ENCROACHMENT
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
LOAD ENCROACHMENT
EVENTS: Disabled
Range: Disabled, Enabled
827846A1.CDR
AN
GL
E
AN
GL
E
–REACH
REACH
LOAD ENCROACHMENT
OPERATE
R
X
LOAD ENCROACHMENT
OPERATE
Summary of Contents for L60
Page 2: ......
Page 4: ......
Page 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Page 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Page 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...