5-106
L60 Line Phase Comparison Relay
GE Multilin
5.5 GROUPED ELEMENTS
5 SETTINGS
5
5.5.6 POWER SWING DETECT
PATH: SETTINGS
GROUPED ELEMENTS SETTING GROUP 1(6)
POWER SWING DETECT
POWER SWING
DETECT
POWER SWING
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
POWER SWING
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
POWER SWING
SHAPE: Mho Shape
Range: Mho Shape, Quad Shape
MESSAGE
POWER SWING
MODE: Two Step
Range: Two Step, Three Step
MESSAGE
POWER SWING
SUPV: 0.600 pu
Range: 0.050 to 30.000 pu in steps of 0.001
MESSAGE
POWER SWING FWD
REACH: 50.00
Ω
Range: 0.10 to 500.00
Ω
in steps of 0.01
MESSAGE
POWER SWING QUAD FWD
REACH MID: 60.00
Ω
Range: 0.10 to 500.00
Ω
in steps of 0.01
MESSAGE
POWER SWING QUAD FWD
REACH OUT: 70.00
Ω
Range: 0.10 to 500.00
Ω
in steps of 0.01
MESSAGE
POWER SWING FWD
RCA: 75°
Range: 40 to 90° in steps of 1
MESSAGE
POWER SWING REV
REACH: 50.00
Ω
Range: 0.10 to 500.00
Ω
in steps of 0.01
MESSAGE
POWER SWING QUAD REV
REACH MID: 60.00
Ω
Range: 0.10 to 500.00
Ω
in steps of 0.01
MESSAGE
POWER SWING QUAD REV
REACH OUT: 70.00
Ω
Range: 0.10 to 500.00
Ω
in steps of 0.01
MESSAGE
POWER SWING REV
RCA: 75°
Range: 40 to 90° in steps of 1
MESSAGE
POWER SWING OUTER
LIMIT ANGLE: 120°
Range: 40 to 140° in steps of 1
MESSAGE
POWER SWING MIDDLE
LIMIT ANGLE: 90°
Range: 40 to 140° in steps of 1
MESSAGE
POWER SWING INNER
LIMIT ANGLE: 60°
Range: 40 to 140° in steps of 1
MESSAGE
POWER SWING OUTER
RGT BLD: 100.00
Ω
Range: 0.10 to 500.00
Ω
in steps of 0.01
MESSAGE
POWER SWING OUTER
LFT BLD: 100.00
Ω
Range: 0.10 to 500.00
Ω
in steps of 0.01
MESSAGE
POWER SWING MIDDLE
RGT BLD: 100.00
Ω
Range: 0.10 to 500.00
Ω
in steps of 0.01
MESSAGE
POWER SWING MIDDLE
LFT BLD: 100.00
Ω
Range: 0.10 to 500.00
Ω
in steps of 0.01
MESSAGE
POWER SWING INNER
RGT BLD: 100.00
Ω
Range: 0.10 to 500.00
Ω
in steps of 0.01
Summary of Contents for L60
Page 2: ......
Page 4: ......
Page 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Page 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Page 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...