GE Multilin
L60 Line Phase Comparison Relay
5-79
5 SETTINGS
5.5 GROUPED ELEMENTS
5
b) 87PC SCHEME
PATH: SETTINGS
GROUPED ELEMENTS PHASE COMPARISON ELEMENTS 87PC SCHEME
87PC SCHEME
87PC FUNCTION:
Disabled
Range: Disabled, Enabled
MESSAGE
87PC SCHEME SELECT:
2TL-TR-SPC-2FC
Range: 2TL-TR-SPC-2FC, 2TL-BL-SPC-2FC,
2TL-TR-DPC-3FC, etc.
MESSAGE
87PC BLOCK:
Off
Range: FlexLogic™ operand
MESSAGE
87PC SIGNAL SOURCE:
One Source Current
Range: One Source Current, Two Sources Current
MESSAGE
87PC SIGNAL:
Mixed I_2-K*I_1
Range: Mixed I_2–K*I_1, 3I_0
MESSAGE
87PC MIXED SIGNAL K:
0.20
Range: 0.00 to 0.25 in steps of 0.01
MESSAGE
87PC FDL PICKUP:
0.50 pu
Range: 0.02 to 15.00 pu in steps of 0.01
MESSAGE
87PC FDL AUX:
Off
Range: FlexLogic™ operand
MESSAGE
87PC FDH PICKUP:
0.75 pu
Range: 0.01 to 15.00 pu in steps of 0.01
MESSAGE
87PC FDH AUX:
Off
Range: FlexLogic™ operand
MESSAGE
87PC CH1 ASYMMETRY:
0.0 ms
Range: –5.0 to 5.0 ms in steps of 0.1
MESSAGE
87PC CH2 ASYMMETRY:
0.0 ms
Range: –5.0 to 5.0 ms in steps of 0.1
MESSAGE
87PC CH1 DELAY:
0.0 ms
Range: 0.0 to 30.0 ms in steps of 0.1
MESSAGE
87PC CH2 DELAY:
0.0 ms
Range: 0.0 to 30.0 ms in steps of 0.1
MESSAGE
87PC CH1 RX VOLT:
12.0 V
Range: 0.0 to 125.0 V in steps of 0.1
MESSAGE
87PC CH2 RX VOLT:
12.0 V
Range: 0.0 to 125.0 V in steps of 0.1
MESSAGE
87PC STABILITY
ANGLE: 75°
Range: 40 to 140° in steps of 5
MESSAGE
87PC RESET DELAY:
30 ms
Range: 0 to 200 ms in steps of 1
MESSAGE
87PC TRANS BLOCK
PICKUP: 0.030 s
Range: 0 to 65.535 s in steps of 0.001
MESSAGE
87PC TRANS BLOCK
RESET: 0.030 s
Range: 0 to 65.535 s in steps of 0.001
MESSAGE
87PC CHNL LOSS TRIP
WINDOW: 0
msec
Range: 0 to 500 ms in steps of 1
Summary of Contents for L60
Page 2: ......
Page 4: ......
Page 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Page 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Page 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...