5 SETTINGS
5.4 FLEXLOGIC™
5
ELEMENT:
Open Pole Detector
OPEN POLE OP
Φ
A
OPEN POLE OP
Φ
B
OPEN POLE OP
Φ
C
OPEN POLE BKR
Φ
A OP
OPEN POLE BKR
Φ
B OP
OPEN POLE BKR
Φ
C OP
OPEN POLE BLK N
OPEN POLE BLK AB
OPEN POLE BLK BC
OPEN POLE BLK CA
OPEN POLE REM OP
Φ
A
OPEN POLE REM OP
Φ
B
OPEN POLE REM OP
Φ
C
OPEN POLE OP
Open pole condition is detected in phase A
Open pole condition is detected in phase B
Open pole condition is detected in phase C
Based on the breaker(s) auxiliary contacts, an open pole condition is
detected on phase A
Based on the breaker(s) auxiliary contacts, an open pole condition is
detected on phase B
Based on the breaker(s) auxiliary contacts, an open pole condition is
detected on phase C
Blocking signal for neutral, ground, and negative-sequence overcurrent
element is established
Blocking signal for the AB phase distance elements is established
Blocking signal for the BC phase distance elements is established
Blocking signal for the CA phase distance elements is established
Remote open pole condition detected in phase A
Remote open pole condition detected in phase B
Remote open pole condition detected in phase C
Open pole detector is operated
ELEMENT:
Phase Directional
Overcurrent
PH DIR1 BLK A
PH DIR1 BLK B
PH DIR1 BLK C
PH DIR1 BLK
Phase A Directional 1 Block
Phase B Directional 1 Block
Phase C Directional 1 Block
Phase Directional 1 Block
ELEMENT:
Phase Distance
PH DIST Z1 PKP
PH DIST Z1 OP
PH DIST Z1 OP AB
PH DIST Z1 OP BC
PH DIST Z1 OP CA
PH DIST Z1 PKP AB
PH DIST Z1 PKP BC
PH DIST Z1 PKP CA
PH DIST Z1 SUPN IAB
PH DIST Z1 SUPN IBC
PH DIST Z1 SUPN ICA
PH DIST Z1 DPO AB
PH DIST Z1 DPO BC
PH DIST Z1 DPO CA
Phase Distance Zone 1 has picked up
Phase Distance Zone 1 has operated
Phase Distance Zone 1 phase AB has operated
Phase Distance Zone 1 phase BC has operated
Phase Distance Zone 1 phase CA has operated
Phase Distance Zone 1 phase AB has picked up
Phase Distance Zone 1 phase BC has picked up
Phase Distance Zone 1 phase CA has picked up
Phase Distance Zone 1 phase AB IOC is supervising
Phase Distance Zone 1 phase BC IOC is supervising
Phase Distance Zone 1 phase CA IOC is supervising
Phase Distance Zone 1 phase AB has dropped out
Phase Distance Zone 1 phase BC has dropped out
Phase Distance Zone 1 phase CA has dropped out
PH DIST Z2 to Z3
Same set of operands as shown for PH DIST Z1
ELEMENT:
Phase
Instantaneous
Overcurrent
PHASE IOC1 PKP
PHASE IOC1 OP
PHASE IOC1 DPO
PHASE IOC1 PKP A
PHASE IOC1 PKP B
PHASE IOC1 PKP C
PHASE IOC1 OP A
PHASE IOC1 OP B
PHASE IOC1 OP C
PHASE IOC1 DPO A
PHASE IOC1 DPO B
PHASE IOC1 DPO C
At least one phase of PHASE IOC1 has picked up
At least one phase of PHASE IOC1 has operated
At least one phase of PHASE IOC1 has dropped out
Phase A of PHASE IOC1 has picked up
Phase B of PHASE IOC1 has picked up
Phase C of PHASE IOC1 has picked up
Phase A of PHASE IOC1 has operated
Phase B of PHASE IOC1 has operated
Phase C of PHASE IOC1 has operated
Phase A of PHASE IOC1 has dropped out
Phase B of PHASE IOC1 has dropped out
Phase C of PHASE IOC1 has dropped out
PHASE IOC2
Same set of operands as shown for PHASE IOC1
ELEMENT:
Phase Overvoltage
PHASE OV1 PKP
PHASE OV1 OP
PHASE OV1 DPO
PHASE OV1 PKP A
PHASE OV1 PKP B
PHASE OV1 PKP C
PHASE OV1 OP A
PHASE OV1 OP B
PHASE OV1 OP C
PHASE OV1 DPO A
PHASE OV1 DPO B
PHASE OV1 DPO C
At least one phase of Overvoltage 1 has picked up
At least one phase of Overvoltage 1 has operated
At least one phase of Overvoltage 1 has dropped out
Phase A of Overvoltage 1 has picked up
Phase B of Overvoltage 1 has picked up
Phase C of Overvoltage 1 has picked up
Phase A of Overvoltage 1 has operated
Phase B of Overvoltage 1 has operated
Phase C of Overvoltage 1 has operated
Phase A of Overvoltage 1 has dropped out
Phase B of Overvoltage 1 has dropped out
Phase C of Overvoltage 1 has dropped out
Table 5–7: L60 FLEXLOGIC™ OPERANDS (Sheet 4 of 7)
OPERAND TYPE
OPERAND SYNTAX
OPERAND DESCRIPTION
Summary of Contents for L60
Page 2: ......
Page 4: ......
Page 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Page 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Page 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...