GE Multilin
L60 Line Phase Comparison Relay
5-49
5 SETTINGS
5.3 SYSTEM SETUP
5
must be programmed to create a logic 0 when the breaker is open. If
BREAKER 1 MODE
is selected as "3-Pole", this set-
ting selects a single input as the operand used to track the breaker open or closed position. If the mode is selected as
"1-Pole", the input mentioned above is used to track phase A and settings
BREAKER 1
Φ
B
and
BREAKER 1
Φ
C
select
operands to track phases B and C, respectively.
•
BREAKER 1(2) FB:
If the mode is selected as 3-pole, this setting has no function. If the mode is selected as 1-pole,
this input is used to track phase B as above for phase A.
•
BREAKER 1(2) FC:
If the mode is selected as 3-pole, this setting has no function. If the mode is selected as 1-pole,
this input is used to track phase C as above for phase A.
•
BREAKER 1(2) EXT ALARM:
Selects an operand, usually an external contact input, connected to a breaker alarm
reporting contact.
•
BREAKER 1(2) ALARM DELAY:
Sets the delay interval during which a disagreement of status among the three pole
position tracking operands will not declare a pole disagreement, to allow for non-simultaneous operation of the poles.
•
MANUAL CLOSE RECAL1 TIME:
Sets the interval required to maintain setting changes in effect after an operator has
initiated a manual close command to operate a circuit breaker.
•
BREAKER 1(2) OUT OF SV:
Selects an operand indicating that Breaker 1(2) is out-of-service.
•
XCBR ST.LOC OPERAND:
Selects a FlexLogic™ operand to provide a value for the IEC 61850 XCBR1(2) St.Loc
data item.
Summary of Contents for L60
Page 2: ......
Page 4: ......
Page 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Page 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Page 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...