5-48
L60 Line Phase Comparison Relay
GE Multilin
5.3 SYSTEM SETUP
5 SETTINGS
5
5.3.4 BREAKERS
PATH: SETTINGS
SYSTEM SETUP
BREAKERS BREAKER 1(2)
A description of the operation of the breaker control and status monitoring features is provided in Chapter 4. Only informa-
tion concerning programming of the associated settings is covered here. These features are provided for two breakers; a
user may use only those portions of the design relevant to a single breaker, which must be Breaker 1.
•
BREAKER 1(2) FUNCTION:
Set to "Enable" to allow the operation of any breaker control feature.
•
BREAKER1(2) PUSH BUTTON CONTROL:
Set to "Enable" to allow faceplate push button operations.
•
BREAKER 1(2) NAME:
Assign a user-defined name (up to 6 characters) to the breaker. This name will be used in
flash messages related to Breaker 1.
•
BREAKER 1(2) MODE:
Selects "3-pole" mode, where all breaker poles are operated simultaneously, or "1-pole" mode
where all breaker poles are operated either independently or simultaneously.
•
BREAKER 1(2) OPEN:
Selects an operand that creates a programmable signal to operate an output relay to open
Breaker No. 1.
•
BREAKER 1(2) CLOSE:
Selects an operand that creates a programmable signal to operate an output relay to close
Breaker No. 1.
•
BREAKER 1(2)
Φ
A/3-POLE:
Selects an operand, usually a contact input connected to a breaker auxiliary position
tracking mechanism. This input can be either a 52/a or 52/b contact, or a combination the 52/a and 52/b contacts, that
BREAKER 1
BREAKER 1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
BREAKER1 PUSH BUTTON
CONTROL: Disabled
Range: Disabled, Enabled
MESSAGE
BREAKER 1 NAME:
Bkr 1
Range: up to 6 alphanumeric characters
MESSAGE
BREAKER 1 MODE:
3-Pole
Range: 3-Pole, 1-Pole
MESSAGE
BREAKER 1 OPEN:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1 CLOSE:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1
φ
A/3-POLE:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1
φ
B:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1
φ
C:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1 EXT ALARM:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1 ALARM
DELAY: 0.000
s
Range: 0.000 to 1 000 000.000 s in steps of 0.001
MESSAGE
MANUAL CLOSE RECAL1
TIME: 0.000
s
Range: 0.000 to 1 000 000.000 s in steps of 0.001
MESSAGE
BREAKER 1 OUT OF SV:
Off
Range: FlexLogic™ operand
MESSAGE
XCBR ST.LOC OPERAND:
Off
Range: FlexLogic™ operand
Summary of Contents for L60
Page 2: ......
Page 4: ......
Page 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Page 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Page 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...