GE KM170 Installation Manual Download Page 1

 

 

 

 

 

© 2003 GE Interlogix B.V.. All rights reserved. 
Version 1-1 / April 2004 

 

55317003 

 

KM170 Carbon Monoxide Detector 

Installation Manual

   

 

 

 

 

 

 

Installation Manual 

 

D

ESCRIPTION

 

The KM170 carbon monoxide (CO) detector is designed for use 
with the KM260 CO detection system in car parks and other 
enclosed spaces where levels of CO gas must be monitored and 
controlled effectively.  
The detection system is designed to detect levels of CO lower than 
those considered safe for human inhalation and so prevent the 
build up of hazardous CO gas. Detection time is less than 10 
seconds. 

I

NSTALLATION

 

Placement of carbon monoxide detectors

 

As CO gas is lighter than air, detectors should be placed just 
above the level where the gas is expected to be generated (above 
40cm in the case of car parks).  
Installing detectors too high or placing detectors too close to 
windows, air inlets or other areas of ventilation may prevent the 
gas from reaching the detector. 

Connection and installation 

 

Wiring diagram:

 

1

 Positive line; 

2

 Data; 

3

 

Negative line. 

 

Locking mechanism:

 

1

 Tab closed (detector head not locked); 

2

 Tab broken (detector head locked).

 

The detector is supplied in 3 parts: the detector head, the detector 
base and the fixing bracket.  
If necessary the fixing bracket can be used as a connection box. 
To install: 
1.  Attach fixing bracket to surface using two 50mm screws. 
2.  Attach detector base to fixing bracket using two 9mm screws. 
3.  Insert detector head into base, push and turn clockwise until 

detector locks into place. 

The detector head may be locked into the base by breaking the 
blocking tab at the base of the detector head (figure 

). To 

remove detector head once the blocking tab has been removed 
insert screwdriver into base slot and push.

 

When in service the detector LED will flash green. A flashing red 
LED indicates fault. A constant red LED indicates alarm (this 
occurs when CO levels of 50 PPM are detected).

 

M

AINTENANCE

 

Fault repair must be carried out by qualified 
personnel. Do not manipulate interior. 

No specific maintenance is required. The following guidelines will 
help ensure your CO detection system remains in good working 
order: 

 

Exposure to strong gases or fumes may damage sensor.  

 

Keep the CO detection system switched on once installed for 
the built-in cleaning system to operate. 

 

Estimated detector lifespan is four years. 

T

ECHNICAL 

C

HARACTERISTICS

 

Input voltage..................................................................... 9 - 20 VDC 
Consumption ............................................................................65 mA 
Reaction time ............................................................................... 10s 
Type of sensor.................................................... TGS semiconductor 
Coverage....................................................up to 300 m² per detector 
Maximum number of detectors per zone........................................ 15 
Service indication ................................................ flashing green LED 
Fault indication ........................................................ flashing red LED 
Alarm indication....................... constant red LED (CO level 50 PPM) 
Dimensions..................................................................81 x Ø109 mm 
Protection index..........................................................................IP 22 
Sensor lifespan....................................................................... 4 years 
Working temperature.......................................................... 0 to 50 

0

Manual de instalación 

 

D

ESCRIPCIÓN

 

El detector de monóxido de carbono (CO) KM170 está diseñado 
para usarse con el sistema de detección de CO KM260 en 

Reviews: