5.1.3
Re-calibrating the Touchscreen
The QuickPanel
+
touchscreen is shipped pre-calibrated. However, If there are any issues
with touchscreen responsiveness, it may need to be re-calibrated.
�
�
To re-calibrate the touchscreen
1.
Open the
Qui Setup
tool.
2.
Select the
TouchPanel
tab.
3.
Select
Recalibrate Touch Screen
.
4.
Select
Recalibrate Touch Sensor
.
Note
During IC755CxW07CDx touchscreen sensor re-calibration, the user is
prompted to activate a switch located in the battery compartment. This is not
applicable to any other panel sizes.
5.
Remove the battery cover and press the switch.
Battery
Cover
Switch
Touchscreen Sensor Calibration Switch
6.
Replace the battery cover.
48
GFK-2847F
Qui Operator Interface User Manual
For public disclosure