GE IC695CMM002CA-EJ Important Product Information Download Page 1

Important Product Information

 

PACSystems* RX3i 

 

IC695CMM002-EJ and IC695CMM002CA-EJ 

IC695CMM004-EJ, IC695CMM004CA-EJ, and IC695CMM004LT-EJ 

GFK-2461N

 

Serial Communications Modules 

April 2018 

 

 

 

 

 
PACSystems* RX3i Serial Communications modules expand the serial 
communications capabilities of the RX3i system.  
Serial Communications module IC695CMM002 provides two independent, 
isolated serial ports. Serial Communications module IC695CMM004, illustrated at 
right, provides four independent, isolated serial ports.  
Up to six Serial Communications modules can be located in the main 
PACSystems RX3i backplane

1

.  

The IC695CMM00xCA modules are the conformal-coated versions of the 
IC695CMM00x modules.  
The IC695CMM004LT version is for low temperature applications (-40°C). 
Each port can be configured for MODBUS Master, MODBUS Slave, CCM Slave, 
DNP3 Master, DNP3 Slave, or Serial I/O protocol. If any port is configured for 
DNP3 Master or Slave, the other ports on the module can only be configured for 
DNP3 Master or Slave. 
For modules with firmware version 1.32 or later, half-duplex flow control can be 
configured using Machine Edition 

Release 5.90, SP1, SIM 6

 or later. Otherwise, 

flow control defaults to full-duplex. 
Additional module features include: 

 

Port-to-port isolation and port-to-backplane isolation  

 

RS-232, RS-485/422 communication, software-selected 

 

Hardware handshake: RTS/CTS, RFR/CTS for RS-232 

 

Selectable Baud Rates: 1200, 2400, 4800, 9600, 19.2K, 38.4K, 57.6K, 115.2K 

 

Module fault status reporting (Watchdog, Ram Fail, Flash Fail) 

 

Module identity and status reporting, including LED status indicators 

 

Meets CE, UL/CUL 508 and 1604, and ATEX requirements 

 

Flash memory for future upgrades  

These modules must be located in an RX3i Universal Backplane.  
RX3i Serial Communications can be hot-inserted and removed following the 
instructions in the most recent version of the 

PACSystems RX3i System Manual

GFK-2314.   
For complete installation information, please refer to RX3i and Series 90-30 
Installation and Maintenance Requirements document, GFK-2975. 

 

Figure 1: CMM004 Front 

View 

 

                                                                    
© 2007-2018 General Electric Company. All Rights Reserved. 
*Indicates a trademark of General Electric Company and/or its subsidiaries. All other trademarks are the property of 
their respective owners. 

1

 Not compatible with Rackless CPUs, such as CPE400. 

Summary of Contents for IC695CMM002CA-EJ

Page 1: ...half duplex flow control can be configured using Machine Edition Release 5 90 SP1 SIM 6 or later Otherwise flow control defaults to full duplex Additional module features include Port to port isolation and port to backplane isolation RS 232 RS 485 422 communication software selected Hardware handshake RTS CTS RFR CTS for RS 232 Selectable Baud Rates 1200 2400 4800 9600 19 2K 38 4K 57 6K 115 2K Mod...

Page 2: ...ly No change in functionality performance or compatibility IC695CMM002 AF IC695CMM004 AF 1 34 44A753277 G06 44A753278 G06 Adds DNP3 0 Master and Slave Unsolicited Reporting functionality The release also adds the ability to configure the DNP3 0 Slave Analog Input Event Variation and fixes three issues in the DNP3 0 firmware IC695CMM002 AE IC695CMM004 AE 1 32 44A753277 G05 44A753278 G05 See GFK 246...

Page 3: ...d to use the CMM CPU Firmware Version Requirements PACSystems RX3i CPU Version 5 50 or newer is required for SPL PACSystems RX3i CPU Version 5 00 or newer is required for DNP3 Master to sync its timestamp value with the CPU PACSystems RX3i CPU Version 3 83 or newer is required to be able to use the CMM in the RX3i system Problems Resolved by Release 2 02 None Problems Resolved by Release 2 01 Issu...

Page 4: ...memory the Q memory address must start on a byte boundary in Q Target Address 1 can be mapped to Q00001 or Q00009 but it can not be mapped to Q00007 6 CCM Slave Read Scratchpad operations may fail when a port is configured for CCM Slave protocol and a new configuration is stored to the PLC using Machine Edition or the system is power cycled or the module is hot inserted If the first query received...

Page 5: ... Other 1 DNP3 0 configurations with Unsolicited Response support enabled or Analog Input Event Variations set to other than 16 Bit Values Without Time will result in a System Configuration Mismatch fault If any of these configuration is downloaded to a module with firmware earlier than Release 1 34 the module configuration will fail 2 The maximum resolution for the MODBUS drop delay is 420μ s so t...

Reviews: