background image

RTD Input Module

GFK-1206D 

 Analog Input Module

2

 June 1997 

   

 

Module Operation

The RTD Input Module accepts four inputs from three-wire or four-wire RTDs and converts
the input level to a digital value. Input spans support a variety of RTD types, as listed in the
Module Specifications section.

The analog/digital converter reads the voltage generated by each of the four inputs. The A/D
converter converts the differential measurement into a binary value (15 bits plus sign),
which is read by the block’s microprocessor. The microprocessor sets the gain required in the
analog/digital converter for each individual input. The gain is based on the RTD type that
has been configured for that input.

The microprocessor selects the input by means of a solid state, optically-coupled multiplexer.
Three measurements are made for each input: Excitation current, RTD resistance including
field wire drop, and field wire drop. From these three measurements, the module calculates
the  RTD resistance. A DC/DC converter circuit isolates the field side from the logic circuits.

46723

Signal

Conditioning

and

Multiplexer

Excitation

Current

A/D

2.5V 

Reference

2.5V

+5 V

–5 V

DC/DC

FLASH

Logic

Opto

Micro–

Regulator

6.5V

Serial Bus

5V

processor

Calibration

The  module  automatically  performs A/D calibration at powerup. Automatic calibration is
then repeated every  minute to compensate for changes in the ambient temperature.

The module stores the calibration constants for each gain in RAM memory. This data can be
read and changed if necessary.

Summary of Contents for IC670ALG620

Page 1: ...re input http www cimtecautomation com parts p 14496 ic670alg620 aspx Provides the wiring diagrams and installation guidelines for this GE Field Control module For further information please contact Cimtec Technical Support at 1 866 599 6507 sales cimtecautomation com ...

Page 2: ...ms H Selectable RTD input as resistance or temperature Celsius or Fahrenheit H Reportshigh low underrange over range open wire and input short alarms H Uses optional discrete inputs and outputs for status and control H Two data acquisition rates based on 50 Hz and 60 Hz line frequencies H Configurable channel activation 46722 1 2 3 4 SLOT Power Sources No loop power is required for this module The...

Page 3: ... has been configured for that input The microprocessor selects the input by means of a solid state optically coupled multiplexer Three measurements are made for each input Excitation current RTD resistance including field wire drop and field wire drop From these three measurements the module calculates the RTD resistance A DC DC converter circuit isolates the field side from the logic circuits 467...

Page 4: ...ms tenths of degrees Fahrenheit or tenths of degrees Celsius This module exchanges data with a BIU in the same manner as other types of I O modules it provides all its input data and status bits when requested by the BIU and receives fault clearing commands from the BIU via its assigned output bits Note that the BIU can be configured not to send status data over the network The module can also be ...

Page 5: ...le s optional fault clearingbitsintheBIU sdiscrete output Q table 8 0 8 Discete Output DataReference Startingoffsetforthemodule soptional fault clearingbitsintheBIU sdiscete outputtable userselectable AnalogOutput Data Length Word length for analog output data in the BIU sanalogoutput AQ table Should not beusedformostapplications 0 0 4 AnalogOutput DataReference Starting offset for the module s an...

Page 6: ...imit If alarm reporting is not wanted alarm limits can be set beyond the dynamic range of the signal so they will never be activated Input Selection to Include RTD Type Each input channel can have a different RTD type selectable from a list of many different RTDs If the actual RTD resistance does not match the defined type an adjustment factor can be configured in tenths of ohms Selection Comments...

Page 7: ...00 100 Ohm Platinum α 00385 27 01 389 936 180 0 850 0 100 Ohm Platinum α 003902 93 5400 135 000 17 7777 99 9999 100 Ohm Platinum IPTS68 PA 26 5 327 744 200 0 630 0 100OhmPlatinumSAMA RC21 4 PC 26 5 311 874 200 0 600 0 100 Ohm Platinum JISC 1604 81 26 5 323 780 200 0 620 0 25 5 Ohm Platinum Lab Std PJ 4 50 83 575 200 0 630 0 9 035 Ohm Copper CA 6 05 16 400 100 0 260 0 50OhmCopper CB 2 28 379 105 78...

Page 8: ...input to logic user input to frame ground 1500VAC for 1 minute 250 VACcontinuous Channel to Channel 250 VACcontinuous Current drawn from BIU power supply 190mA maximum DigitalResolution 15 bits plus sign Operatingtemperaturerange 0 to 55 Degrees C ambient Channel Characteristics RTDtypes 10 25 100 and 1000 ohm platinum 10 and 100 ohm copper 100 50 and 120 ohm nickel 604 ohms and 1000 ohms nickel i...

Page 9: ...er module Each terminal can accommodate one or two wires up to AWG 14 avg 2 1mm2 cross section TheI OTerminal Block with Connectors IC670CHS003 has one 20 pin male connector per module I O Terminal Block with Box Terminals IC670CHS002 and 102 I O Terminal Block with Barrier Terminals IC670CHS001 and 101 Ter minals E1 E2 E4 E6 and E8 are electrically connected together A1 and A2 are electrically co...

Page 10: ...overrange RTD 2 Input underrange RTD 3 Input overrange RTD 3 Input underrange RTD 4 Input overrange RTD 4 7 6 5 4 3 2 1 0 Open Wire RTD 1 Circuit Diagnostics Bits byte 2 Open Wire RTD 2 Open Wire RTD 3 Open Wire RTD 4 Shorted input RTD 1 Shorted input RTD 2 Shorted input RTD 3 Shorted input RTD 4 7 6 5 4 3 2 1 0 Wiring error RTD 1 Circuit Diagnostics Bits byte 3 Wiring error RTD 2 Wiring error RTD...

Page 11: ......

Reviews: