8
8-4
User manual IC220SDL953 - September 2011
GFK-2731
8.1
Safe digital output errors
Acknowledge all errors that are present. Only then can the outputs be re-enabled.
Acknowledgment: Yes (1)
Acknowledging the diagnostic message deletes the message. The module can only be
restarted following power up and error-free selftest.
Table 8-4
Safe output errors
Error cause
Diagnostic
code (hex)
LED
Remark
Effect
Remedy
Acknow-
ledgment
Hardware
fault
X01n
All
OUT:
Red
ON
The indicated output
cannot be disabled
All module outputs
are in the safe state
Power up with error-
free selftest
Replacement
Yes (1)
X010: OUT0_Ch1
X011: OUT1_Ch1
X012: OUT2_Ch1
X013: OUT3_Ch1
X017: OUT0_Ch2
X018: OUT1_Ch2
X019: OUT2_Ch2
X01A: OUT3_Ch2
Short circuit
or overload
X03n
OUTy
: Red
ON
Affected output is in
the safe state
Check actuator
Check connector
and cabling
Check free running
circuit at the
contactor
Yes (2)
X030: OUT0_Ch1
X031: OUT1_Ch1
X032: OUT2_Ch1
X033: OUT3_Ch1
X037: OUT0_Ch2
X038: OUT1_Ch2
X039: OUT2_Ch2
X03A: OUT3_Ch2
Error at the
output
or short
circuit during
the test
X05n
All
OUT:
Red
ON
Pulse test (brief
activation) at the
output failed
All module outputs
are in the safe state
Power up with error-
free selftest
Replacement
Yes (1)
X050: OUT0_Ch1
X051: OUT1_Ch1
X052: OUT2_Ch1
X053: OUT3_Ch1
X057: OUT0_Ch2
X058: OUT1_Ch2
X059: OUT2_Ch2
X05A: OUT3_Ch2
Error at the
output
during the
test
X06n
All
OUT:
Red
ON
Pulse test (brief
deactivation) at the
output failed
All module outputs
are in the safe state
Power up with error-
free selftest
Replacement
Yes (1)
X060: OUT0_Ch1
X061: OUT1_Ch1
X062: OUT2_Ch1
X063: OUT3_Ch1
X067: OUT0_Ch2
X068: OUT1_Ch2
X069: OUT2_Ch2
X06A: OUT3_Ch2
Hardware
fault
X091
All
OUT:
Red
ON
Detected by internal
tests.
All module outputs
are in the safe state
Power up with error-
free selftest
Replacement
Yes (1)
Cross circuit
at the
indicated
output
X0An
All
OUT:
Red
ON
Cross circuit with
another output or
with an external
signal
All module outputs
are in the safe state
Remove error
Power up with error-
free selftest
Yes (1)
X0A0: OUT0_Ch1
X0A1: OUT1_Ch1
X0A2: OUT2_Ch1
X0A3: OUT3_Ch1
X0A7: OUT0_Ch2
X0A8: OUT1_Ch2
X0A9: OUT2_Ch2
X0AA: OUT3_Ch2