Assembly and removal of the safety module
Assembly
•
Disconnect the power to the station.
– Snap on base
•
Before snapping on the safety module, remove the inserted connectors from the safety
terminal and the adjacent connector from the neighboring VersaPoint terminal on the
left. This prevents the potential routing knife contacts and the keyway/featherkey
connections from being damaged.
•
Hold the safety module perpendicular and snap it onto the DIN rail (7.5 mm in height).
Figure 4-2
Snapping on the safety module base
•
Check that all the snap-on mechanisms are securely snapped into place.
– Insert connectors
•
Insert the connectors in the specified order (A, B).
Figure 4-3
Inserting the connector
For general information about assembling and removing VersaPoint terminals, please
refer to the GFK-2736 user manual.
–
Set the DIP switches prior to assembly (see "Setting the DIP switches" on page 4-2).
The DIP switches cannot be accessed when the safety module is installed in the
VersaPoint station.
–
Observe a mounting distance of 30 mm above and 40 mm below the safety module.
Shorter distances may inhibit proper handling during installation.
Ensure that
all
featherkeys and keyways on adjacent terminals are
securely
interlocked.
1A
1B
Only use the connectors supplied with the module or connectors that are approved as
replacement items (see "Ordering data: Accessories" on page 10-7).
B