B 1
Checklists for the VersaSafe system
B 1.1
Planning
Checklist for planning the use of the VersaSafe system
Equipment identification
Date
Author
Test engineer
Remark
No. Requirement (mandatory)
Yes
Remark
1
Has a hazard and risk analysis been carried out for the system/machine?
2
Has the corresponding safety integrity level (
SIL, SIL CL, Cat., PL) been
derived from the hazard and risk analysis
?
3
Does the VersaSafe system meet the required safety integrity level?
4
Has the current IC220SDL953 user manual been used as the basis for
planning?
Revision:
5
Has the voltage supply been planned according to the specifications for the
protective extra-low voltage in accordance with PELV?
6
Are safety distances that must be observed calculated according to the
response and delay times implemented?
7
Has the required shutdown time for the safety function t
SF
resulting from the
machine/system design been determined?
t
SF
:
8
Can the planned application be implemented with the configuration options
(e.g., by using function blocks)?
9
Does the planned use correspond to the intended use of the system?
10
Has the technical data of the VersaSafe system been observed?
11
Has it been ensured that in an overall system comprising the VersaSafe
system and any higher-level PROFIsafe system, the addresses (address
within the VersaSafe system and F-Address of the PROFIsafe system) are
unique?
12
Within a VersaSafe system, is each island number only assigned once?
13
Is the application stop (OFF, STOP, emergency stop, triggering of safety
equipment) implemented according to EN 60204?
14
When planning the safety functions, has the VersaConf Safety software tool
been used to determine whether the memory space is sufficient for the size of
the safety logic?
15
Has it been ensured that any person intentionally starting hazardous
movements has a direct view of the danger zone?