Page 43
Hydran* M2 Installation Guide
16375 v9.0 Oct 12
Installing the Cover
Figure 34: Installing the Cover
When installing the cover, the 4 screws must be tightened correctly.
A minimum torque of 50 lbf-in (5.6 N-m) is recommended. Failure to
do so may result in water ingress inside the enclosure.
CAUTION
CAUTION
Gasket must be
properly in place
1.
Put cover back in place.
2.
Insert the four (4) screws with flat washers and split
lock washers. Using supplied Hex key tool, tighten
the screws one by one diagonally.