Chapter 11 • Operating the Hydran 201
i
System
11-2
Rev. 6, March 2011
Part 17997
Note: With this method, the analog outputs and the alarm contacts are not connected to a
SCADA system.
11.1.1.1
Method Drawbacks
The
periodic, visual monitoring
method has a deficient response time following the
detection of an alarm; this response time cannot be inferior to the period of time between
two inspections. The Hydran 201
i
System, however, has a response time measured in
minutes.
11.1.2 Alarm Monitoring
The
alarm monitoring
method solves the disadvantages of the
periodic, visual monitoring
method as follows:
• Connecting the alarm contacts to an alarm panel (or any other SCADA system) located
in the station’s control room.
• Continuous alarm monitoring.
• Periodic, visual reading (weekly) of the gas level on the display of the Hydran 201T
i
’s
or the Hydran 201C
i
-1. For details on the various methods of data reading, see
• Manual logging of the gas level readings.
For details on the alarms and relays operation, see Chapter 10.
11.1.2.1
Method Drawbacks
The
alarm monitoring
method solves the response time inadequacy of the
periodic, visual
monitoring
method (Section 11.1.1 on page 11-1), but does not provide any information to
anticipate and prevent alarms.
Moreover, no information is available to immediately evaluate the severity of this alarm.
For example, a rapid gas level increase and a daily trend increase trigger the same alarm.
These two alarm conditions, however, do not have the same importance.
Summary of Contents for Hydran 201i
Page 1: ...GE Energy Services Digital Energy Hydran Instruction Manual 201i System ...
Page 6: ...Instruction Manual vi Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 8: ...Instruction Manual viii Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 22: ...Instruction Manual xxii Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 36: ...Chapter 1 Introduction 1 10 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 114: ...Chapter 5 Before Installation 5 16 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 143: ...Installation Part 17997 Rev 6 March 2011 6 29 Figure 6 9 Installing the CPU Module ...
Page 236: ...Chapter 12 Troubleshooting 12 20 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 244: ...Chapter 13 Maintenance 13 8 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 254: ...Appendix B Mechanical Drawings B 2 Rev 6 March 2011 Part 17997 Figure B 3 1 5 In Adaptor ...
Page 255: ...Hydran 201Ti Intelligent Transmitter Part 17997 Rev 6 March 2011 B 3 Figure B 4 1 In Adaptor ...
Page 284: ...Appendix G Unit Conversions G 2 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 298: ...Appendix I Glossary I 12 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 299: ......