Chapter 10 • Alarms
10-14
Rev. 6, March 2011
Part 17997
2.
Acknowledge the alarm using the H201T
i
’s keypad or the Hydran Host software. For
the procedure, see Section 4.2.1 on page 4-3, and the
Hydran Host Software Manual
.
If the problem has been corrected since a period of time exceeding the corresponding
alarm delay, the alarm message then disappears from the H201T
i
’s display;
otherwise, it simply stops flashing and remains on the display.
3.
Press the Hydran 201C
i
-1’s corresponding push-button.
10.5
FAIL ALARM
The fail alarm generally indicates to the user that there is a problem with the
Hydran 201
i
System, not with the transformer. A fail alarm must therefore be verified and
solved rapidly because it indicates that the
protection
system of the transformer is not
functioning properly.
10.5.1 Fail Alarm Triggering
If the fail alarm relay is set to the
Normal
or
Latch
mode, the fail alarm is triggered (the
fail alarm relay is de-energized) when one of the following alarm conditions occurs:
• Supervisory link broken between the Hydran 201T
i
and the Hydran 201C
i
Controller.
This condition is the only one that affects
only
the fail alarm relay of the Hydran 201C
i
-1.
All other conditions affect the fail alarm relays of both the H201T
i
and the H201C
i
-1.
• ac power failure or partial failure (power voltage too low for the H201T
i
to function
properly).
• Unable to restart the microprocessor.
• H201T
i
not initialized (no alarm message appears on the H201T
i
’s display for this
condition). To cancel this alarm, enter the information requested on the H201T
i
’s display
(for details, see Section 4.2.5 on page 4-6).
• More than 20 “watchdogs” occurred in 15 minutes (no alarm message appears on the
H201T
i
’s display for this condition).
• Detection of a hardware malfunction during the autoverification phase of the initial-
ization (no alarm message appears on the H201T
i
’s display for this condition).
•
Setup Lost
(for details, see Section 12.1.24 on page 12-13).
• One of the fault triggers conditions, listed in Table 10-1 on page 10-3 (for details, see
Summary of Contents for Hydran 201i
Page 1: ...GE Energy Services Digital Energy Hydran Instruction Manual 201i System ...
Page 6: ...Instruction Manual vi Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 8: ...Instruction Manual viii Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 22: ...Instruction Manual xxii Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 36: ...Chapter 1 Introduction 1 10 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 114: ...Chapter 5 Before Installation 5 16 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 143: ...Installation Part 17997 Rev 6 March 2011 6 29 Figure 6 9 Installing the CPU Module ...
Page 236: ...Chapter 12 Troubleshooting 12 20 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 244: ...Chapter 13 Maintenance 13 8 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 254: ...Appendix B Mechanical Drawings B 2 Rev 6 March 2011 Part 17997 Figure B 3 1 5 In Adaptor ...
Page 255: ...Hydran 201Ti Intelligent Transmitter Part 17997 Rev 6 March 2011 B 3 Figure B 4 1 In Adaptor ...
Page 284: ...Appendix G Unit Conversions G 2 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 298: ...Appendix I Glossary I 12 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 299: ......