Chapter 8 • Hydran 201C
i
-1 Installation
8-12
Rev. 6, March 2011
Part 17997
8.3.3
Installing the Cable Conduits
Note the following considerations prior to installing:
• All cables connected to the Hydran 201C
i
-1 must be run through steel conduits.
Otherwise, armored cables can be used.
• Flexible rather than rigid conduits should be used near the H201C
i
-1 to ease installation
and servicing.
• Conduits, or cable armors, should be made of steel to shield against magnetic fields.
The procedure is as follows:
1.
Remove the rubber plugs from the required openings of the H201C
i
-1 enclosure.
2.
For each cable being used, install a standard watertight conduit fitting (not supplied).
Up to six conduits may be installed (supervisory link, ac power supply, alarms and
analog outputs).
3.
Mount a conduit to each fitting.
4.
Ground the conduits and/or cable shields at some point. Follow the company
regulations meticulously.
8.3.4
Installing the Supervisory Link Cable
Note: The supervisory link cable has already been run into a conduit up to the
Hydran 201Ci-1 if the installation of the Hydran 201Ti is completed (see Section 6.3.9 on
page 6-26).
1.
If required, trim the excess length from the end of the supervisory link cable from the
H201T
i
.
Note: The total maximum length of the supervisory link cable connected to a H201Ci-1 is
1,200 m (4,000 ft).
2.
Ensure the six wires have been labelled (for identification purposes) at both ends.
3.
Connect the cable wires and shield to the H201C
i
-1’s termination board. For wiring
details, see Table D-11 on page D-8.
Summary of Contents for Hydran 201i
Page 1: ...GE Energy Services Digital Energy Hydran Instruction Manual 201i System ...
Page 6: ...Instruction Manual vi Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 8: ...Instruction Manual viii Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 22: ...Instruction Manual xxii Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 36: ...Chapter 1 Introduction 1 10 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 114: ...Chapter 5 Before Installation 5 16 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 143: ...Installation Part 17997 Rev 6 March 2011 6 29 Figure 6 9 Installing the CPU Module ...
Page 236: ...Chapter 12 Troubleshooting 12 20 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 244: ...Chapter 13 Maintenance 13 8 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 254: ...Appendix B Mechanical Drawings B 2 Rev 6 March 2011 Part 17997 Figure B 3 1 5 In Adaptor ...
Page 255: ...Hydran 201Ti Intelligent Transmitter Part 17997 Rev 6 March 2011 B 3 Figure B 4 1 In Adaptor ...
Page 284: ...Appendix G Unit Conversions G 2 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 298: ...Appendix I Glossary I 12 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 299: ......