Chapter 8 • Hydran 201C
i
-1 Installation
8-8
Rev. 6, March 2011
Part 17997
2.
Set the parameter
RelayMode
of the System Fault relay to
Off
.
3.
On the H201C
i
-1, verify that:
• The display goes blank.
• The two door-mounted push-button indicators (
1
and
2
) remain lit.
• The
System OK
indicator (yellow, DS11; item 16 in Figure 3-7 on page 3-12) turns off.
• The
System OK
alarm NO contact is open.
• The
System OK
alarm NC contact is closed.
• The gas alarm indicators (yellow DS9 and DS10) and contacts are restored to their
normal state (no alarm condition).
• If connected, the SCADA system has detected the alarm.
Note: Pushing both push-buttons to acknowledge the gas alarm conditions should turn off
the indicators since the conditions are cleared during a system fault.
8.2.4.4
System Fault Alarm Cleared
1.
Set the same
RelayMode
parameter to
Normal
.
2.
On the H201C
i
-1, verify that:
• The H201C
i
-1’s display is functional again.
• The two door-mounted push-button indicators (
1
and
2
) are lit because the gas alarm
conditions still exist.
• The
System OK
indicator (yellow, DS11; item 16 in Figure 3-7 on page 3-12) is lit.
• The
System OK
alarm NO contact is closed.
• The
System OK
alarm NC contact is open.
• If connected, the SCADA system has detected the state change of the fail alarm relay.
Note: Pushing both push-buttons to acknowledge the gas alarm conditions should not turn
off the indicators since the conditions are not cleared.
8.2.4.5
Gas Alarms Cleared
1.
Access the submenu
Relays/Analog;GasH Relay
.
2.
Set the parameter
RelayMode
of this relay to
Normal
.
Summary of Contents for Hydran 201i
Page 1: ...GE Energy Services Digital Energy Hydran Instruction Manual 201i System ...
Page 6: ...Instruction Manual vi Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 8: ...Instruction Manual viii Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 22: ...Instruction Manual xxii Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 36: ...Chapter 1 Introduction 1 10 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 114: ...Chapter 5 Before Installation 5 16 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 143: ...Installation Part 17997 Rev 6 March 2011 6 29 Figure 6 9 Installing the CPU Module ...
Page 236: ...Chapter 12 Troubleshooting 12 20 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 244: ...Chapter 13 Maintenance 13 8 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 254: ...Appendix B Mechanical Drawings B 2 Rev 6 March 2011 Part 17997 Figure B 3 1 5 In Adaptor ...
Page 255: ...Hydran 201Ti Intelligent Transmitter Part 17997 Rev 6 March 2011 B 3 Figure B 4 1 In Adaptor ...
Page 284: ...Appendix G Unit Conversions G 2 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 298: ...Appendix I Glossary I 12 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 299: ......