9.1
Ordering Accessories and Replacement Parts
The following data are required for an order:
- Type designation
on nameplate
- Serial number
on nameplate
- Instruction manual number
on cover
- Figure number and position number in the figure
- Part description
- Quantity required
9.2
Inspection
The circuit breaker may remain in operation during inspection.
9.2.1
Visual Inspection
• Check the circuit breaker carefully for damage or corrosion. In
particular, check the insulators from the ground for possible
damage.
• If corrosion is detected, take steps to prevent or control corrosion.
• Check the ventilation ports and vents in the mechanism cabinet to
make sure they are clear. Remove any blockages.
9.2.2
Anti-Condensation Heater
Check the heat dissipation from the anti-condensation heater. To
do so, place a contact thermometer on the anti-condensation hea-
ter and measure the temperature rise.
9.2.3
Checking Gas Pressure
Check the density monitor indicator. If the indicator is not in the
green area, top up with gas until rated pressure is reached
“Filling the Breaker with Gas” on Page 56)
.
Danger due to electric shock.
Therefore:
- Never reach into the high voltage insulation area of the
circuit breaker.
- Never touch the contacts of the circuit breaker control
system.
Follow all regional and operator-specified safety precautions.
DANGER
The anti-condensation heating unit gets hot during operation.
It can burn skin or clothing.
Therefore:
- Never touch the heating unit directly.
CAUTION
Summary of Contents for GL 311 F3/4031 P/VE
Page 2: ......
Page 10: ...INTRODUCTION 10 146 OI 250 EN REV7 REV6...
Page 12: ...SAFETY 12 146 OI 250 EN REV7 REV3...
Page 48: ...INSTALLATION 48 146 OI 250 EN REV7 REV7...
Page 80: ...INSPECTION AND MAINTENANCE 80 146 OI 250 EN REV7 REV3...
Page 102: ...RECONDITIONING 102 146 OI 250 EN REV7 REV7...
Page 104: ...END OF LIFE MANAGEMENT 104 146 OI 250 EN REV7 REV2a...
Page 114: ...SPECIAL EQUIPMENT OPTIONAL 114 146 OI 250 EN REV7 REV0...
Page 128: ...REPLACEMENT PARTS AND ACCESSORIES 128 146 OI 250 EN REV7 REV6...
Page 130: ...HANDLING USED SULFUR HEXAFLUORIDE 130 146 OI 250 EN REV7 REV2...